General Data - Trane RTWD Installation Operation & Maintenance

Series r helical rotary water-cooled liquid and compressor chillers
Table of Contents

Advertisement

Table 1 - RTWD Standard Effi ciency - R134a
Indicative performances
Cooling Capacity (1)
Total Power input in cooling (1)
Heating Capacity (2)
Total Power input in heating (2)
Compressor
Compressor Number per Circuit
Type
Model
Evaporator
Quantity
Type
Evaporator model
Evaporator Water Content volume
Two pass evaporator
Evap. Water Flow rate - Minimum (3)
Evap. Water Flow rate - Maximum (3)
Nominal water connection size (Grooved coupling) (in) - (mm)
Three pass evaporator
Evap. Water Flow rate - Minimum (3)
Evap. Water Flow rate - Maximum (3)
Nominal water connection size (Grooved coupling) (in) - (mm)
Condenser
Quantity
Type
Condenser model
Condenser Water Content volume
Two pass condenser
Cond. Water Flow rate - Minimum
Cond. Water Flow rate - Maximum
Nominal water connection size (Grooved coupling) (in) - (mm)
Dimensions (4)
Unit Length
Unit Width
Unit Height
Weights (5)
Shipping Weight
Operating Weight
System data (6)
Nb of refrigerant circuit
Minimum cooling load %
Standard unit
R134a refrigerant charge Circuit1 / Circuit 2 (6)
Oil charge Circuit1 / Circuit 2
POE Oil type
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser water temperature 30°C/35°C - for detailed performances consult
order write up.
(2) Indicative performance at Evaporator water temperature: 10°C / 7°C - Condenser water temperature 40°C/45°C - for detailed performances consult
order write up.
(3) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(4) These dimensions are the maximum for a specifi c size, they may vary from one confi guration to another within a same size. For accurate
dimensions of a specifi c confi guration, refer to relevant submittal drawings.
(5) All weights +/-5% and are the maximum for each size and may vary from one confi guration to another for the same size (add 62kg for unit with
acoustic package) and refer to relevant drawing for a specifi c confi guration.
(6) System data are indicative and subject to change without notice. Please refer to unit nameplate data.
RLC-SVX14H-GB
RTWD
160
(kW)
582.0
(kW)
133.0
(kW)
568.3
(kW)
138.3
#
1/1
M2/N1
#
Flooded shell and tube heat exchanger
E3BM2
(l)
69.4
(l/s)
8.4
(l/s)
30.7
5 1"
(139.7 mm)
(139.7 mm)
(l/s)
5.6
(l/s)
20.4
4"
(114.3 mm)
(114.3 mm)
#
Shell and Tube Heat Exchanger
C3BM2
(l)
87.5
(l/s)
11.0
(l/s)
40.4
6"
(168.3 mm)
(168.3 mm)
(mm)
3490
(mm)
1310
(mm)
1970
(kg)
3718
(kg)
3874
#
2
%
30
(kg)
65/67
(l)
9.9/11.7
11.7/11.7

General data

RTWD
RTWD
170
190
642.0
700.0
149.0
161.0
624.2
679.8
154.1
167.0
1/1
1/1
Screw
N1/N1
N1/N2
1
E3BM1
E3BM1
75.5
84.0
9.3
10.6
34.1
38.9
5 1"
5 1"
(139.7 mm)
(139.7 mm)
6.2
7.1
22.7
25.9
4"
4"
(114.3 mm)
(114.3 mm)
1
C3BM2
C3BM1
93.6
102.9
12.1
13.6
44.2
49.9
6"
6"
(168.3 mm)
(168.3 mm)
3490
3490
1310
1310
1970
1970
3881
3900
4049
4086
2
2
30
30
65/65
65/67
11.7/11.7
OIL048E or OIL023E
RTWD
200
769.0
174.0
746.8
181.7
1/1
N2/N2
E3BMJ
90.1
11.5
42.3
5 1"
7.7
28.2
4"
C3BMJ
111.1
15.0
55.0
6"
3490
1310
1970
3924
4125
2
30
65/66
11.7/11.7
9