4 INPUT/OUTPUT CONPOSITE MODULE
Type
Specifications
Number of output points
Insulation method
Rated load voltage
Max. load current
Max. rush current
Leakage current at OFF
Max. voltage drop at ON
Response
OFF ON
time
ON OFF
Surge killer
Fuse
Fuse breakage indication
External
Voltage
power supply
Current
Common terminal
arrangement
3: When the external power supply is turned off, fuse breakage is not detected.
4 - 4
(2) Transistor Output Specifications (Sink Type)
Provided (When fuse is broken, LED lights and a signal is output to CPU) 3
QX48Y57 I/O Module (Output Specification)
7 points
Photocoupler
12-24VDC (+20/-15%)
0.5A/point, 2A/common
4A/10ms or less
0.1mA or lower
0.2VDC (TYP.) 0.5A, 0.3VDC (MAX.) 0.5A
1ms or shorter
1ms or shorter (rated load, resistance load)
Zener diode
4A (Not replaceable) (Fuse breakage capacity: 50A)
12-24VDC (+20/-15%) (ripple ratio within 5%)
10mA (at 24VDC)
7 points/common (common terminal: TB18)
MELSEC-Q
4 - 4