Mitsubishi Electric QX10 User Manual page 15

Melsec system q programmable logic controllers
Hide thumbs Also See for QX10:
Table of Contents

Advertisement

1
GENERAL SPECIFICATIONS OF INPUT AND OUTPUT MODULES AND
INSTRUCTIONS FOR SELECTING THEM
1 - 4
(9) Tighten the module fixing and terminal block screws to the torques in the following
ranges.
Screw Location
Module fixing screw (M3 12 screw)
I/O module terminal block screw (M3 screw)
I/O module terminal block mounting screw (M3 screw)
(10)There are the following restrictions on the thermal protections activated by
protected output modules.
The thermal protections are overload and overheat protective functions.
(a) QY40P, QY41P, QY42P, QH42P
Function
Common
(Overload and overheat
protective functions)
Overload protective
function
Overheat protective
function
• If an overcurrent keeps flowing due to overload, heat is generated
to activate the overheat protective function.
• Each protective function is designed to protect the internal
elements of the module, not the external equipment.
• The overload protective function is activated in 1 point increments
in terms of 1A to 3A/point.
• The overload protective function returns operation to normal when
the load becomes a rated load
• The overheat protective function is activated in 1 point increments.
• The overheat protective function automatically returns operation to
normal when heat reduces.
MELSEC-Q
Tightening Torque Range
36 to 48 N•cm
42 to 58 N•cm
66 to 89 N•cm
Description
1 - 4