Parameter assignment/addressing

4.1

Parameters

DQ 4×24..230VAC/2A ST parameters
The table below lists the parameters that can be set. The effective range of the configurable
parameters depends on the type of configuration. The following configurations are possible:
● Central operation with an ET 200SP CPU
● Distributed operation on PROFINET IO in an ET 200SP system
● Distributed operation with PROFIBUS DP in an ET 200SP system
When performing the configuration in the user program, use the "WRREC" instruction to
transfer the parameters to the module using data records (refer to the section Parameter
assignment and structure of parameter data record (Page 21)).
The following parameter settings are possible:
Table 4- 1
Configurable parameters and their defaults (GSD file)
Parameter
Operating mode •
Channel activated
Channel deactivated
Reaction to
Turn off
CPU STOP
Keep last value
Output substitute value 1
Only for configuration using the PROFIBUS GSD file; does not affect configuration with STEP 7 using HSP: As the
1
number of parameters with PROFIBUS GSD configuration is limited to a maximum of 244 bytes per ET 200SP station,
the configuration options are limited. If required, however, you can still set this parameter using data record 128 as de-
scribed in the column "GSD file PROFINET IO" (see the table above). The parameter length of the I/O module is 3
bytes.
DQ 4x24..230VAC/2A ST digital output module (6ES7132-6FD00-0BB1)
Manual, 03/2015, A5E32043575-AB
Range of values
Channel
activated
Turn off
Default
Recon-
Effective range with configuration software, e.g.
figuration
in RUN
GSD file PROFINET IO GSD file PROFIBUS DP
Yes
Channel
Yes
Channel
STEP 7 (TIA Portal)
Channel
Module
4
1
12