Packaged terminal air conditioners and heat pumps
Table of Contents

Advertisement

TYPICAL WALL AND DEEP WALL INSTALLATION
NOTES:
1. Sleeve may be flush mounted to floor, but front panel may
have to be notched to accommodate service cord.
2. If more than 4 in. of sleeve projects into room, an accessory
subbase must be used for support.
3. For walls 2 in. thick or less, an accessory subbase must be
used for support.
Typical Wall Installation
NOTES:
1. To permit outdoor grille to be attached to and supported
by unit sleeve, fabricate a sleeve extension so unit sleeve
and baffles can reach outdoor grille. Be sure to provide
flashing for proper condenser runoff to avoid water dam-
age to room interior. Internal or external drain system may
be required.
2. Baffles may be part of the sleeve extension or fixed
directly to condenser coil tube sheets.
3. Caulk all joints between sleeve or baffles and opening in
wall.
4. If grille is used on outdoor wall opening, do not install an
additional outdoor grille on unit sleeve.
Typical Deep Wall Installation
25