Cable Routing In Enclosures - ABB S800 I/O User Manual

Hide thumbs Also See for S800 I/O:
Table of Contents

Advertisement

!!%% 8hivr‡ÃD‡r…hyÃ8hiyr†
D‡r€
Row of cabinets
Cabinet parts
(plates)
Grounding in
cabinet
Temperature in
cabinet
Radio emission
Shielded cable
Internal cables
3BSE 020 923R101
Brr…hyÃDs‚…€h‡v‚ÃhqÃD†‡hyyh‡v‚ÃV†r…¶†ÃBˆvqr
Uhiyr !' 8hivr‡†ÃD‡r…hyÃ8hiyr†Ã
8‚pr…vt
Electrical connection
(grounding)
All parts electrically
connected to each other
and to the PE bar
Design
Max. permitted
temperature for
continued operation.
Emission
Design
Routing
Trp‡v‚Ã!!% 8urpxyv†‡†
8urpx
Through short 35 mm
conductors joining the PE terminals in
each cabinet.
R < 100 mΩ
Only one single grounding system for
ABB Advant equipment.
@Y8@QUDPIT
Max. permitted temperature for
continued operation in cabinet is +5 to
+55°C
(41 to 131°F).
Measured just below the I/O module.
Modules on compact MTUs on a vertical
DIN rail allow +5 to +40°C (41 to 104°F)
ambient temperature.
S800 equipment does not require radio
proof enclosures.
Communication, pulse transducers and
analog circuits for Low Level (RTD Pt,
thermocouples) must be shielded up to
the S800 I/O modules
See
Section 2.2.3, Cable Routing in
Enclosures.
Check that there is no tension in the
wiring.
2
(2 AWG) copper
IPÃ
59