Row of cabinets
Cabinet parts
(plates)
Grounding in
cabinet
Temperature in
cabinet
Radio emission
Shielded cable
Internal cables
3BSE 020 923R101
Brr
hyÃDs
hvÃhqÃDhyyhvÃVr
¶ÃBvqr
Uhiyr !' 8hivrÃDr
hyÃ8hiyrÃ
8pr
vt
Electrical connection
(grounding)
All parts electrically
connected to each other
and to the PE bar
Design
Max. permitted
temperature for
continued operation.
Emission
Design
Routing
TrpvÃ!!% 8urpxyv
8urpx
Through short 35 mm
conductors joining the PE terminals in
each cabinet.
R < 100 mΩ
Only one single grounding system for
ABB Advant equipment.
@Y8@QUDPIT
Max. permitted temperature for
continued operation in cabinet is +5 to
+55°C
(41 to 131°F).
Measured just below the I/O module.
Modules on compact MTUs on a vertical
DIN rail allow +5 to +40°C (41 to 104°F)
ambient temperature.
S800 equipment does not require radio
proof enclosures.
Communication, pulse transducers and
analog circuits for Low Level (RTD Pt,
thermocouples) must be shielded up to
the S800 I/O modules
See
Section 2.2.3, Cable Routing in
Enclosures.
Check that there is no tension in the
wiring.
2
(2 AWG) copper
IPÃ
59