6! U7'$U7'%ÃH‚qˆyr7ˆ†Ã8hiyrÃ6qhƒ‡r…Pˆ‡D
Arh‡ˆ…r†
• Passive unit used for connection and extension of the
ModuleBus
• DIN rail mounting.
9r†p…vƒ‡v‚
The TB805 ModuleBus Cable Adaptor-Out and TB806
ModuleBus Cable Adaptor-In with the ModuleBus
Extension Cables, TK801V0xx, are used to extend the
ModuleBus.
Using the TB805 and TB806, I/O modules on the same
electrical ModuleBus of an I/O cluster, can be mounted
on different DIN rails. This makes the installation of I/O
Modules more flexible when laying out an enclosure
design. Please refer to
S800 I/O
for details on layouts.
The ModuleBus extension cables used with the
TB805/TB806 comes in 3 standard lengths:
• VTK801V003 - 300 mm
• TK801V006 - 600 mm
• TK801V012 - 1.2 meters.
Overall ModuleBus length must not exceed 2.5 meters
including all cables and MTUs.
The TB805/TB806 mounts on the standard DIN rail.
It has a mechanical latch that locks it to the rail. It is
grounded to the DIN-rail through a metallic spring
connector. The latch can be released with a screwdriver.
3BSE 020 923R101
Trp‡v‚Ã6! U7'$U7'%ÃH‚qˆyr7ˆ†Ã8hiyrÃ6qhƒ‡r…Pˆ‡D
Section 2.1.4.1, I/O Station with
Brr…hyÃDs‚…€h‡v‚ÃhqÃD†‡hyyh‡v‚ÃV†r…¶†ÃBˆvqr
TB805 ModuleBus
Connector (X1)
DB25 Male
Connector (X2)
1
14
DB25 Female
Connector (X2)
25
13
TB806 ModuleBus
Connector (X1)
13
25
14
1
111