Do not ground the same circuit at different points in the plant.
B
qvtÃsÃ6 qqvvhyÃ@vr
Additional power supply units of different types used by loads or sensor, and
modems and so on, and are located in the controller or I/O cabinet, shall be treated
in the following way with respect to grounding:
•
The apparatus chassis (PE terminal) shall be connected to the installation
protective earth terminal or directly to cabinet chassis if the apparatus chassis
and bounding are accepted for protective bounding.
•
No circuitry of an equipment shall be completely electrically floating but
referenced to a suitable potential.
!!" 8hiyrÃSvtÃvÃ@py
rÃ
There are some restrictions in mixing cables within a cabinet due to the risk of
interference.To describe the simple rules applicable at site installation, cables are
divided in categories. See
installations:
•
Within a category cables can be arbitrary mixed.
•
The distance between cables belonging to different categories shall be kept >
50 mm (2").
•
"Cabinet internal" junctions have their own defined spaces for routing.
Distance to other cables should always be > 50 mm (2").