Actuator Mounting - Fisher Z500 Instruction Manual

Severe service ball valve
Hide thumbs Also See for Z500:
Table of Contents

Advertisement

Instruction Manual
D103803X012
Figure 6. Use Packing Flange
8. Bolt up the packing flange. Use Belleville washers in the same orientation as removed. Contact your
office
or Local Business Partner for additional information. Make sure that the markings on the studs and nuts are
facing out. Tighten the nuts in a star pattern (figure 2). Tighten the nuts with applicable torque (table 6).
Figure 7. Bolt Up the Packing Flange

Actuator Mounting

CAUTION
Never use a hammer or excessive force to install the shaft adapter on the valve. Improper installation can cause permanent
damage to the valve.
1. Mount the shaft adapter on top of the shaft with the two keys. Make sure it fits onto the shaft easily without
hammering.
2. Position the mounting bracket onto the body. Use anti-seize lubricant on the bracket studs and nuts. Make sure the
markings on the studs and nuts are facing out. Leave the nuts.
Z500 Valve
July 2017
Emerson sales