MODBUS
Error
Code
Illegal Data Value
Data value does not match MODBUS
0216
specification
(i.e. Write Single Coil [5H] value other than
OFF [0000H] or ON [FF00H])
Illegal Instruction Use
0217
ADPRW command used in Slave mode
(D8401 or D8421 bit 4 ON)
ADPRW User Command Error
The PLC source/destination device of the
ADPRW command is invalid or the occupied
PLC device range exceeds the valid area
0218
Details:
H-Byte: 0
L-Byte: 1-5 according to the invalid parameter
Error Name and Details
of the ADPRW command
S
S
/
D
4
Master
Related Devices:(M & D)
/ Slave
Slave
See above
Slave
See above
See above
Master
AND
M8067 set to ON D8067
set to 6705 or 6706
to
12 Troubleshooting
12.6 MODBUS Error Code List
Corrective Action
See Corrective
Actions for Error
Code 207.
Do not use the
ADPRW command in
the MODBUS Slave.
Verify that the
command is within
the Master
Specivication and
device range.
109