Kwh Meter Hardware Functions - E-Mon Class 2000 Installation Instructions Manual

Kwh & kwh/demand
Table of Contents

Advertisement

CLASS 2000 METER

6.3 KWh Meter Hardware Functions

IDR Jack
Calibration Jack
Error LED
Meter Pulse LED
Power On LED
Pulse Output
6.4 Class 1000 and Class 2000 Pulse Output
Removable Two-Screw Terminal Plug
PULSE VALUE GUIDE FOR CLASS 1000 & 2000, KWH & OR KW DEMAND METER
Color Code Key of Sensor Arrow Must Match the Amperage of Meter:
Purple
White
25 Amp
50 Amp
Watt Hours per Pulse
0.48828
0.97656
Pulse output signal is a 50/50 duty cycle. There is no voltage present at the pulse
output connection. It is a solid state relay, and there is no polarity associated with the
relay. The interface range is from 4.5 to 28 VDC, with a maximum of 50 mA.
62-0389-03
8-pin RJ-45-used to connect kWh meter to the E-Mon
Energy automatic meter reading system.
Connector J11 is for factory calibration only, and is not
a user accessible port. Silicon plug is not to be
removed.
When lit, indicates that the current sensor is backwards
or on the incorrect phase.
Blinks to show the meter load. Blink rate increases with
load.
When lit, indicates power to meter is on.
Optically isolated output pulse for connection to BAS or
peripheral equipment.
Brown
Red
100 Amp 200 Amp 400 Amp 800 Amp 1600 Amp 3200 Amp
1.95312
3.90625
22
Yellow
Black
7.81250
15.6250
Blue
Two Blue
31.2500
62.500