Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
control
code
01: TK1 oil circuit trouble
02: TK2 oil circuit trouble
04: TK4 oil circuit trouble
05: TK5 oil circuit trouble
H16
H16
L02
L02
L03
L04
L04
L05
No. of priority indoor
units
L06
L06
L07
L08
L08
Location
of
Description
System status
detection
I/F
Oil level
All stop
detection
circuit trouble
Indoor
Outdoor units
Stop of
unit
model
corresponding
disagreement
unit
trouble
Indoor
Duplicated
Stop of
unit
indoor header
corresponding
unit
unit
I/F
Duplicated
All stop
outdoor line
address
I/F
Duplicated
All stop
priority indoor
unit (as
displayed on
priority indoor
unit)
I/F
Duplicated
All stop
priority indoor
unit (as
displayed on
indoor unit other
than priority
indoor unit)
Indoor
Connection of
Stop of
unit
group control
corresponding
cable to
unit
standalone
indoor unit
Indoor
Indoor group /
Stop of
unit
addresses not
corresponding
set
unit
Trouble detection
condition(s)
No temperature change is detected
by TK1 despite compressor 1
having been started.
No temperature change is detected
by TK2 despite compressor 2
having been started.
No temperature change is detected
by TK4 despite compressor having
been started.
No temperature change is detected
by TK4 despite compressor having
been started.
In case of different outdoor unit
(Not corresponded to Air to Air
Heat Exchanger type)
There are more than one header
units in group.
There is duplication in line address
setting for outdoor units belonging
to different refrigerant piping
systems.
More than one indoor units have
been set up as priority indoor unit.
More than one indoor units have
been set up as priority indoor unit.
There is at least one standalone
indoor unit to which group control
cable is connected.
Address setting has not been
performed for indoor units.
– 63 –
Check items (locations)
• Check for disconnection of TK1
sensor.
• Check resistance characteristics
of TK1 sensor.
• Check for connection trouble
involving TK1, TK2, , TK4, and
TK5 sensors
• Check for clogging in oil
equalizing circuit capillary and
faulty operation in check valve.
• Check for refrigerant entrapment
inside compressor.
• Check for disconnection of TK2
sensor.
• Check resistance characteristics
of TK2 sensor.
• Check for connection trouble
involving TK1, TK2, , TK4, and
TK5 sensors
• Check for clogging in oil
equalizing circuit capillary and
faulty operation in check valve.
• Check for refrigerant entrapment
inside compressor.
• Check for disconnection of TK4
sensor.
• Check resistance characteristics
of TK4 sensor.
• Check for connection trouble
involving TK1, TK2, , TK4, and
TK5 sensors
• Check for clogging in oil
equalizing circuit capillary and
faulty operation in check valve.
• Check for refrigerant entrapment
inside compressor.
• Check for disconnection of TK5
sensor.
• Check resistance characteristics
of TK5 sensor.
• Check for connection trouble
involving TK1, TK2, , TK4, and
TK5 sensors
• Check for clogging in oil
equalizing circuit capillary and
faulty operation in check valve.
• Check for refrigerant entrapment
inside compressor.
• Check outdoor unit model.
(Check whether the outdoor unit
corresponds to Air to Air Heat
Exchanger type or not.)
• Check indoor addresses.
• Check for any change made to
remote control connection
(group/individual) since indoor
address setting.
• Check line addresses.
• Check display on priority indoor
unit.
• Check displays on priority indoor
unit and outdoor unit.
• Check indoor addresses.
• Check indoor addresses.
Note:
This code is displayed when
power is turned on for the first
time after installation.