Refrigerating Cycle Diagram - Toshiba MML-AP0124H2UL Service Manual

Carrier
Hide thumbs Also See for MML-AP0124H2UL:
Table of Contents

Advertisement

5. REFRIGERATING CYCLE DIAGRAM

Liquid side
Gas side
Strainer
Pulse Motor
Valve (PMV)
Sensor
(TC2)
Functional part name
Pulse Motor Valve
Temp. sensor
Capillary tube
Strainer
Sensor
(TCJ)
PMV
(Connector CN082 (6P): Blue)
1) Controls super heat in cooling operation
2) Controls subcool in heating operation
3) Recovers refrigerant oil in cooling operation
4) Recovers refrigerant oil in heating operation
1. TA
(Connector CN104 (2P): White)
1) Detects indoor suction temperature
2. TC1
(Connector CN100 (3P): Brown)
1) Controls PMV super heat in cooling operation
3. TC2
(Connector CN101 (2P): Blue)
1) Controls PMV subcool in heating operation
4. TCJ
(Connector CN102 (2P): Yellow)
1) Controls PMV super heat in cooling operation
Air heat exchanger
at indoor side
Fan
Sensor
M
(TA)
Functional outline
– 19 –
Sensor
(TC1)
Fan motor

Advertisement

Table of Contents
loading

Table of Contents