Function CODE No. (DN Code) Table (Includes All Functions Needed to Perform Applied Control on Site)
DN
Item
Filter display delay timer
01
02 Dirty state of filter
03 Central control address
04 Specific indoor unit
priority
Heating temp shift
06
0d Existence of [AUTO]
mode
0F Cooling only
10 Type
11 Indoor unit capacity
12 Line address
13 Indoor unit address
14 Group address
28 Automatic restart of
power failure
2A Selection of option/
trouble input (CN070)
2E HA terminal (CN061)
select
31 Ventilating fan control
32 TA sensor selection
33 Temperature unit select
60 Timer setting
(wired remote control)
77 Dual set point
92 Outside interlock
release condition
B3 Soft cooling
C6 Secondary Heating off
outside temperature
Secondary Heating off
C7
outside temperature
differential
Secondary Heating
dB
ON/OFF differential
temperature
Secondary Heating
dC
operate start differential
temperature
Fd Priority operation mode
(FS unit)
FE FS unit address
Type
DN code "10"
Value
Type
0010
Floor Console Exposed
0011
Floor Console Recessed
*1 Default value stored in EEPROM mounted on service P.C. board
0000: None
0002: 2500H
0004: 10000H
0000: Standard
0001: High degree of dirt (Half of standard time)
0001: No.1 unit
to
0099: Unfixed
0000: No priority
0000: No shift
to
0002: +2°C (+3.6°F)
0000: Provided
0001: Not provided (Automatic selection from connected outdoor unit)
0000: Heat pump
0001: Cooling only (No display of [AUTO] [HEAT])
0010 : Floor Console Exposed
0011 : Floor Console Recessed
0000: Unfixed
0001: No.1 unit
to
0001: No.1 unit
to
0000: Individual
0002: Follower unit of group
0000: None
0000: Filter input
0002: External interlock
0000: Usual
0002: Fire alarm input
0000: Unavailable
0000: Body TA sensor
0000: °C
0000: Available (can be performed)
0001: Unavailable (cannot be performed)
0000 : Unavailable
0000: Operation stop
0001: Release com munica tion signal receive
0000 : Unavailable
-0015 : -15°C (5°F)
to
0000 : Unavailable
0001 : +0.5°C (+0.9°F)
to
0000 : Unavailable
0000 : Heating
0001 : No.1 unit
0064 : No.64 unit
Model
MML-AP
H2UL
MML-AP
BH2UL
Description
0001: 150H
0003: 5000H
0064: No.64 unit
0001: Priority
0001: +1°C (+1.8°F)
0010: +10°C (+18°F)
(Up to +6 recommended)
0001 to 0034
0030: No.30 unit
0064: No.64 unit
0001: Header unit of group
0001: Restart
0001: Alarm input (Option parts)
0001: Leaving-ON prevention control
0001: Available
0001: Remote control sensor
0001: °F : (at factory shipment)
0002 : Available
0001 : Available
0015 : 15°C (59°F)
0001 : -1°C (-1.8°F) to 0010 : -10°C (-18°F)
0010 : +5°C (+9°F)
0001 : +0.5°C (+0.9°F) to 0010 : +5°C (+9°F) 0000 : Unavailable
0001 : Cooling
0099 : Unfixed
Indoor Unit Capacity
DN code "11"
Value
Capacity
0000*
Invalid
0001
007 type
0003
009 type
0005
012 type
*1 Default value stored in EEPROM mounted on service
P.C. board
– 34 –
At shipment
According to type
0000: Standard
0099: Unfixed
0000: No priority
0002: +2°C (+3.6°F)
(Floor type 0000)
0001: Not provided
0000: Heat pump
According to capacity
type
0099: Unfixed
0099: Unfixed
0099: Unfixed
0001: Restart
0002: External interlock
0000: Usual
(HA terminal)
0000: Unavailable
0000: Body TA sensor
0001: °F
0000: Available
0000 : Unavailable
0000: Operation stop
0001 : Available
0000 : 0°C (+32°F)
0000 : Unavailable
0006 : +3°C (+5.4°F)
0000 : Heating
0099 : Unfixed
Value
Capacity
0007
015 type
0009
018 type
0010
021 type
0011
024 type