Toshiba MML-AP0124H2UL Service Manual page 21

Carrier
Hide thumbs Also See for MML-AP0124H2UL:
Table of Contents

Advertisement

No.
Item
4
Automatic
capacity control
5
Fan speed
selection
Outline of specifications
1) Based on the difference between TA and TS, the
operation capacity is determined by the outdoor unit.
COOL
TA
˚F (˚C)
+3.6 (+2)
SD
SB
+1.8 (+1)
S9
S7
Ts
S5
S3
S0
– 1.8 (– 1)
1) Operation with (HH), (H), (L) or [AUTO] mode is carried
out by the command from the remote control.
2) When the fan speed mode [AUTO] is selected, the fan
speed varies by the difference between TA and TS.
<COOL>
TA ˚F (˚C)
+5.4 (+3.0)
HH
+4.5 (+2.5)
<HH>
+3.6 (+2.0)
H <HH>
+2.7 (+1.5)
H <HH>
+1.8 (+1.0)
L <H>
+0.9 (+0.5)
L <H>
Tsc
L <H>
– 0.9 (– 0.5)
L <L>
< > : Indicate automatic cooling.
• Thermostat-off control by a wired remote control
sensor is the same as thermostat-off control by an
indoor unit sensor.
• If the fan speed has been changed once, it is not
changed for 3 minutes. However when the air
volume changes the fan speed changes.
• When cooling operation has started, select a
downward slope for the fan speed, that is, the high
position.
• If the temperature is just on the difference boundary,
the fan speed does not change.
HEAT
TA
˚F (˚C)
+1.8 (+1)
S3
S0
S5
Ts
S7
S9
– 1.8 (– 1)
SB
SD
– 3.6 (– 2)
SF
A
B
C
D
E
F
G
– 21 –
Remarks
TS: Setup temp.
TA: Room temp.
HH > H > L > UL
Code No. 32
0000: TA sensor of Indoor
unit
0001: TA sensor of wired
remote control