METREL OmegaPAT XA MI 3360 Instruction Manual

METREL OmegaPAT XA MI 3360 Instruction Manual

Hide thumbs Also See for OmegaPAT XA MI 3360:
Table of Contents

Advertisement

OmegaPAT XA
MI 3360

Instruction manual

Ver. 1.2.2, Code no. 20 752 658

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the OmegaPAT XA MI 3360 and is the answer not in the manual?

Questions and answers

Summary of Contents for METREL OmegaPAT XA MI 3360

  • Page 1: Instruction Manual

    OmegaPAT XA MI 3360 Instruction manual Ver. 1.2.2, Code no. 20 752 658...
  • Page 2 LVD, ROHS regulations © 2017 Metrel The trade names Metrel, Smartec, Eurotest, Autosequence are trademarks registered or pending in Europe and other countries No part of this publication may be reproduced or utilized in any form or by any means without...
  • Page 3: Table Of Contents

    MI 3360 OmegaPAT XA Table of contents ABLE OF ONTENTS General description ......................7 Warnings and notes ......................7 1.1.1 Safety warnings ...................... 7 1.1.2 Warnings related to safety of measurement functions .......... 8 1.1.2.1 Flash HV ......................8 1.1.2.2 Differential leak., Ipe leak., Touch leak., Ileak (W-PE), Primary leak., Power, Leak’s &...
  • Page 4 MI 3360 OmegaPAT XA Table of contents 4.10.2.5 Deleting a Workspace / Export ................ 34 4.10.2.6 Importing a Workspace ..................35 4.10.2.7 Exporting a Workspace ..................36 Auto Sequence® groups ....................37 4.11 Auto Sequence® groups menu ................37 4.11.1 4.11.1.1 Operations in Auto Sequence®...
  • Page 5 MI 3360 OmegaPAT XA Table of contents 6.2.8 Touch Leakage ..................... 87 6.2.9 Power ........................89 6.2.10 Leak's & Power ..................... 90 6.2.11 PRCD test ......................91 6.2.12 RCD test ....................... 93 6.2.13 PE conductor (PRCD) ..................95 6.2.14 Open conductor (PRCD) ..................96 6.2.15 PRCD PE probe test .....................
  • Page 6 Generic tag format ...................... 150 Default list of Auto Sequences® ..............152 Appendix D Appendix E Programming of Auto Sequences® on Metrel ES Manager ......153 Auto Sequence® Editor workspace ................153 Managing groups of Auto Sequences® ..............154 Auto Sequence® Name, Description and Image editing ........156 E.2.1...
  • Page 7: General Description

     Use only standard or optional test accessories supplied by your distributor!  Only test equipment provided or approved by Metrel should be connected to 3- PHASE ADAPTER connector.  Do not connect external voltage to CLAMP inputs. It is intended only for connection of Clamps approved by Metrel.
  • Page 8: Warnings Related To Safety Of Measurement Functions

    MI 3360 OmegaPAT XA General description 1.1.2 Warnings related to safety of measurement functions 1.1.2.1 Flash HV  A voltage of up to 3 kV between FLASH and mains socket LN terminals / 1.5 kV between main socket’s LN and PE socket terminals / 1.5 kV between FLASH and mains socket PE terminal is applied to the instrument’s outputs during the test.
  • Page 9: Power Management

    MI 3360 OmegaPAT XA General description 1.2 Power management 1.2.1 230 V / 110 V operation The instrument works on 110 V and 230 V mains. 110 V and 230 V appliances can be fully tested. In UK and Aus/Nz models only 110 V mains voltage will be applied to the mains test socket if the 110 V test adapter (A 1474) is connected to the instrument.
  • Page 10 MI 3360 OmegaPAT XA General description Electromagnetic compatibility (EMC) EN 61326-1 Electrical equipment for measurement, control and laboratory use - EMC requirements – Part 1: General requirements Class B (Portable equipment used in controlled EM environments) Safety (LVD) EN 61010-1 Safety requirements for electrical equipment for measurement, control, and laboratory use –...
  • Page 11: Instrument Set And Accessories

    Calibration Certificate  Short form instruction manual  CD with instruction manual (full version) and PC SW Metrel ES Manager 2.2 Optional accessories See the attached sheet for a list of optional accessories that are available on request from your distributor.
  • Page 12: Instrument Description

    MI 3360 OmegaPAT XA Instrument description 3 Instrument description 3.1 Front panel Figure 3.1: Left side panel Figure 3.2: Front panel...
  • Page 13 MI 3360 OmegaPAT XA Instrument description Mains supply connector F1, F2 fuses (T 16 A / 250 V) Clamp inputs Barcode scanner and RFID / NFC reader / writer device serial port PC / Printer serial port Fuse checker MicroSD card slot USB communication port Escape key / reset key Keypad...
  • Page 14: Instrument Operation

    MI 3360 OmegaPAT XA Instrument operation 4 Instrument operation The instrument can be manipulated via a keypad or touch screen. 4.1 General meaning of keys Cursor keys are used to: select appropriate option RUN key is used to: confirm selected option start and stop measurements Escape key is used to: return to previous menu without changes...
  • Page 15: Virtual Keyboard

    MI 3360 OmegaPAT XA Instrument operation 4.3 Virtual keyboard Figure 4.1: Virtual keyboard Options: Toggle case between lowercase and uppercase. Active only when alphabetic characters’ keyboard layout selected. Backspace Clears last character or all characters if selected. (If held for 2 s, all characters are selected). Enter confirms new text.
  • Page 16: Symbols And Messages

    MI 3360 OmegaPAT XA Instrument operation  Any external voltage against earth on mains test socket  Excessive leakage currents through measuring I/O’s,  Too low resistance between L and N of tested device,  Proper operation of safety relevant internal electronic circuits If a safety check fails, an appropriate warning message will be displayed and safety measures will be taken.
  • Page 17 MI 3360 OmegaPAT XA Instrument operation Select YES to proceed with or NO to cancel measurement. Warning for proper connection in some PRCD measurements. Connection of PRCD’s plug must be changed in order to proceed. Select YES to retry after reconnection with or NO to cancel measurement.
  • Page 18 MI 3360 OmegaPAT XA Instrument operation The load current higher than 16 A is detected. Measurement is aborted. Press OK to continue. The average load current higher than 10 A over the last 5 min test interval is detected. Measurement is stopped. Recovery period for cooling is required before proceeding with tests! Press OK to continue.
  • Page 19 MI 3360 OmegaPAT XA Instrument operation Warning! A very high voltage is / will be present on the instrument output! (Flash test voltage). Test leads resistance in Continuity / Protective Earth measurement is not compensated. Test leads resistance in Continuity / Protective Earth measurement is compensated.
  • Page 20: Instrument Main Menu

    MI 3360 OmegaPAT XA Instrument operation 4.6 Instrument main menu From the instrument Main Menu different main operation menus can be selected. Figure 4.2: Main menu Options Single Tests Menu with single tests, see chapter 0 Error! Not a valid result for able..
  • Page 21: General Settings

    MI 3360 OmegaPAT XA Instrument operation 4.7 General settings In the General Settings menu general parameters and settings of the instrument can be viewed or set. Figure 4.3: Setup menu Options in General Settings menu Language Instrument language selection. Date / Time Instruments Date and time.
  • Page 22: Language

    MI 3360 OmegaPAT XA Instrument operation 4.7.1 Language In this menu the language of the instrument can be set. Figure 4.4: Select language menu 4.7.2 Date and time In this menu date and time of the instrument can be set. Figure 4.5: Setting data and time menu 4.7.3 Profiles Refer to Chapter 4.9 Instrument profiles for more information.
  • Page 23: Settings

    MI 3360 OmegaPAT XA Instrument operation 4.7.6 Settings Figure 4.6: Settings menu Setting options: Description ON – touch screen is active. Touch screen OFF – touch screen is deactivated. ON – sound is active. Keys & touch sound OFF – sound is deactivated. Increment –...
  • Page 24: Initial Settings

    MI 3360 OmegaPAT XA Instrument operation are considered. The Power result measured at the time of worst Idiff is displayed.  In the function Riso, Riso-S the worst case of Riso and Riso-S are considered. The Um result measured at the time of worst Riso is displayed.
  • Page 25: User Accounts

    MI 3360 OmegaPAT XA Instrument operation Figure 4.8: Instrument info screen Note:  Adapter info is also displayed if connected. 4.7.9 User Accounts The demand to sign in can prevent from unauthorized persons to work with the instrument. In this menu user accounts can be managed: Setting if signing in to work with the instrument is required or not.
  • Page 26: Changing User Password, Signing Out

    MI 3360 OmegaPAT XA Instrument operation Options User signing in The user should be selected first. The last used user is displayed in the first row. Goes to Password entry menu. To sign in, the selected user password must be entered and confirmed.
  • Page 27: Managing Accounts

    MI 3360 OmegaPAT XA Instrument operation Enters procedure for changing the user’s password. The actual password must be entered first followed by the new password. Enters the Account manager menu. The Account manager menu is accessed by selecting Account Manager in Sign in menu or User profile menu. The administrator password must be entered and confirmed first.
  • Page 28 MI 3360 OmegaPAT XA Instrument operation The actual password must be entered first followed by the new password. Enters menu for editing user accounts. Figure 4.12: Edit accounts menu Options Opens the window for adding a new user account. In the Add New window the name and initial password of the new user account are to be set.
  • Page 29: Devices

    MI 3360 OmegaPAT XA Instrument operation 4.8 Devices In this menu operation with external devices is configured. Figure 4.13: Devices settings menu Writing devices Type Sets appropriate writing device (Serial printer, Bluetooth printer), RFID writer). Port Sets/views communication port of selected writing device. Bluetooth device Goes to menu for pairing with selected Bluetooth device.
  • Page 30: Instrument Profiles

    MI 3360 OmegaPAT XA Instrument operation 4.9 Instrument profiles In this menu the instrument profile can be selected from the available ones. Figure 4.14: Instrument profile menu The instrument uses different specific system and measuring settings in regard to the scope of work or country it is used.
  • Page 31: Workspace Manager

    4.10.1 Workspaces and Exports The works with OmegaPAT XA MI 3360 can be organized with help of Workspaces and Exports. Exports and Workspaces contain all relevant data (measurements, parameters, limits, structure objects) of an individual work.
  • Page 32: Operations With Workspaces

    MI 3360 OmegaPAT XA Instrument operation Options List of Workspaces. Displays a list of Exports. Adds a new Workspace. Refer to Chapter 4.10.2.3 Adding a new Workspace for more information. List of Exports. Displays a list of Workspaces. 4.10.2.1 Operations with Workspaces Only one Workspace can be opened in the instrument at the same time.
  • Page 33: Operations With Exports

    MI 3360 OmegaPAT XA Instrument operation 4.10.2.2 Operations with Exports Figure 4.18: Workspace manager File menu Options Deletes the selected Export. Refer to chapter 4.10.2.5 Deleting a Workspace / Export for more information. Imports a new Workspace from Export. Refer to chapter 4.10.2.6 Importing a Workspace for more information. Opens options in control panel / expands column.
  • Page 34: Opening A Workspace

    MI 3360 OmegaPAT XA Instrument operation  After confirmation a new Workspace is added in the list in Main Workspace Manager menu. 4.10.2.4 Opening a Workspace  Workspace can be selected from a list in Workspace manager screen.  Opens a Workspace in Workspace manager. The opened Workspace is marked with a blue dot.
  • Page 35: Importing A Workspace

    MI 3360 OmegaPAT XA Instrument operation Before deleting the selected Workspace / Export the user is asked for confirmation.  Workspace / Export is removed from the Workspace / Export list. 4.10.2.6 Importing a Workspace  Select an Export file to be imported from Workspace Manager Export list.
  • Page 36: Exporting A Workspace

    MI 3360 OmegaPAT XA Instrument operation 4.10.2.7 Exporting a Workspace  Select a Workspace from Workspace manager list to be exported to an Export file.  Enters option Export. Before exporting the selected Workspace, the user is asked for confirmation. ...
  • Page 37: Auto Sequence® Groups

    Instrument operation 4.11 Auto Sequence® groups The Auto Sequences® in OmegaPAT XA MI 3360 can be organized by using lists. In a list a group of similar Auto Sequences® is stored. The Auto Sequence® groups menu is intended to manage with different lists of Auto Sequences® that are stored on the microSD card.
  • Page 38: Operations In Auto Sequence® Groups Menu

    MI 3360 OmegaPAT XA Instrument operation 4.11.1.1 Operations in Auto Sequence® groups menu Options Opens the selected list of Auto Sequences®. Previously selected list of Auto Sequences® will be closed automatically. Refer to chapter 4.11.1.2 Selecting a list of Auto Sequences® for more information.
  • Page 39: Deleting A List Of Auto Sequences

    MI 3360 OmegaPAT XA Instrument operation 4.11.1.3 Deleting a list of Auto Sequences®  A list of Auto Sequences® to be deleted can be selected from the Auto Sequence® groups menu.  Enters option for deleting a list. Before deleting the selected list of Auto Sequences®...
  • Page 40: Memory Organizer

    MI 3360 OmegaPAT XA Memory Organizer 5 Memory Organizer Memory Organizer is a tool for storing and working with test data. 5.1 Memory Organizer menu The data is organized in a tree structure with Structure objects and Measurements. OmegaPAT XA has a multi-level structure. The hierarchy of Structure objects in the tree is shown on Figure 5.1.
  • Page 41: Structure Objects

    MI 3360 OmegaPAT XA Memory Organizer at least one single test in the Auto sequence was carried out and there were no other passed or failed single tests empty Auto sequence with empty single tests 5.1.2 Structure Objects Each Structure object has: ...
  • Page 42: Selecting An Active Workspace In Memory Organizer

    MI 3360 OmegaPAT XA Memory Organizer One or more measurement result(s) under selected structure object has failed. Not all measurements under selected structure object have been made yet. Figure 5.4: Example of status - Measurements not completed with fail result(s) measurements under selected...
  • Page 43: Adding Nodes In Memory Organizer

    MI 3360 OmegaPAT XA Memory Organizer Choose desired Workspace from a list of  Workspaces.  Use Select button to confirm selection New Workspace is selected and displayed on the  screen. 5.1.4 Adding Nodes in Memory Organizer Structural Elements (Nodes) are used to ease organization of data in the Memory Organizer. One Node is a must;...
  • Page 44: Operations In Tree Menu

    MI 3360 OmegaPAT XA Memory Organizer Change name of the Node if necessary and  press Add to confirm.  New Structure Element (Node) will be added. 5.1.5 Operations in Tree Menu In the Memory organizer different actions can be taken with help of the control panel at the right side of the display.
  • Page 45: Operations On Structure Objects

    MI 3360 OmegaPAT XA Memory Organizer Starts a new measurement. The instrument goes to the measurement start screen. Refer to chapters 6.1.1.1 Single test start screen and 7.2.1 Auto Sequence® view menu for more information. Saves a measurement. Saving of measurement on a position after the selected (empty or finished) measurement.
  • Page 46 MI 3360 OmegaPAT XA Memory Organizer Sequence® selection screen. Refer to Chapters 6.1 Selection modes and 7.1 Selection of Auto Sequences® for more information. Saves a measurement. Saving of measurement under the selected Structure object. View / edit parameters and attachments. Parameters and attachments of the Structure object can be viewed or edited.
  • Page 47: View / Edit Parameters And Attachments Of A Structure Object

    MI 3360 OmegaPAT XA Memory Organizer 5.1.5.3 View / Edit parameters and attachments of a Structure object The parameters and their content are displayed in this menu. To edit the selected parameter tap on it or press RUN key to enter menu for editing parameters. Parameters Figure 5.8: Example of View / Edit parameters menu Procedure and options...
  • Page 48 MI 3360 OmegaPAT XA Memory Organizer  Select Attachments in Control panel. Attachments  The name of attachment can be seen. Operation with attachments is not supported in the instrument.  Select Comments in Control panel.  View or edit comments Complete comment (if exists) attached to the structure object can be seen on this screen.
  • Page 49: Add A New Structure Object

    MI 3360 OmegaPAT XA Memory Organizer 5.1.5.4 Add a new Structure Object This menu is intended to add new structure objects in the tree menu. A new structure object can be selected and then added in the tree menu. Add Structure Figure 5.9: Add a new Structure Object menu Procedure and options ...
  • Page 50 MI 3360 OmegaPAT XA Memory Organizer  Parameters of the Structure object can be edited.  Adds the selected structure object in the tree menu. Returns to the tree menu without changes.  New object added.
  • Page 51: Add A New Measurement

    MI 3360 OmegaPAT XA Memory Organizer 5.1.5.5 Add a new measurement In this menu new empty measurements can be set and then added in the structure tree. The type of measurement, measurement function and its parameters are first selected and then added under the selected Structure object.
  • Page 52 MI 3360 OmegaPAT XA Memory Organizer  Select parameter and modify it as described earlier. Refer to Chapter 6.1.1.2 Setting parameters and limits of single tests for more information.  Adds the measurement under the selected Structure object in the tree menu. Returns to the structure tree menu without changes.
  • Page 53: Clone A Structure Object

    MI 3360 OmegaPAT XA Memory Organizer 5.1.5.6 Clone a Structure object In this menu selected structure object can be copied (cloned) to same level in the structure tree. Cloned structure object have same name as original. Clone Figure 5.11: Clone Structure Object menu Procedure and options ...
  • Page 54: Clone A Measurement

    MI 3360 OmegaPAT XA Memory Organizer 5.1.5.7 Clone a measurement By using this function a selected empty or finished measurement can be copied (cloned) as an empty measurement to the same level in the structure tree. Procedure and options  Select the measurement to be cloned.
  • Page 55 MI 3360 OmegaPAT XA Memory Organizer  Select Paste option from control panel. Paste  Paste structure object menu displayed. Before copying it can be set which sub-elements of the selected structure object will be copied too. For more details see options below.
  • Page 56: Copy & Paste A Measurement

    MI 3360 OmegaPAT XA Memory Organizer 5.1.5.9 Copy & Paste a measurement In this menu selected measurement can be copied to any allowed location in the structure tree. Procedure  Select the measurement to be copied.  Select Copy option from control panel. Copy ...
  • Page 57: Delete A Structure Object

    MI 3360 OmegaPAT XA Memory Organizer 5.1.5.10 Delete a Structure object In this menu selected Structure object can be deleted. Procedure  Select the structure object to be deleted.  Select Delete option from control panel. Delete  A confirmation window will appear. ...
  • Page 58: Rename A Structure Object

    MI 3360 OmegaPAT XA Memory Organizer  Select Delete option from control panel. Delete  A confirmation window will appear.  Selected measurement is deleted.  Returns to the tree menu without changes. 5.1.5.12 Rename a Structure object In this menu selected Structure object can be renamed. Procedure ...
  • Page 59: Recall And Retest Selected Measurement

    MI 3360 OmegaPAT XA Memory Organizer 5.1.5.13 Recall and Retest selected measurement Procedure  Select the measurement to be recalled.  Select Recall results in control panel. Recall results  Measurement is recalled. Parameters and limits can be viewed but cannot be edited.
  • Page 60: Searching In Memory Organizer

    MI 3360 OmegaPAT XA Memory Organizer  Results / sub-results after re-run of recalled measurement.  Select Save results in control panel. Save results Retested measurement is saved under same structure item as original one. Refreshed memory structure with the new performed measurement is displayed.
  • Page 61 MI 3360 OmegaPAT XA Memory Organizer  The search can be narrowed by entering a text in the Name and Equipment ID fields. Strings can be entered using the on-screen keyboard. Note: The Search function on Equipment ID is case sensitive.
  • Page 62 MI 3360 OmegaPAT XA Memory Organizer Options Next page. Previous page. Note: Search result page consist of up to 50 results. Figure 5.13: Search results screen with structure object selected Options Goes to location in Memory Organizer. View / edit parameters and attachments. Parameters and attachments of the Structure object can be viewed or edited.
  • Page 63: Single Tests

    MI 3360 OmegaPAT XA Single tests 6 Single tests Single tests can be selected in the Main single test menu or in Memory Organizer’s main and submenus. 6.1 Selection modes In Single tests main menu Area group and two different modes for selecting single tests are available.
  • Page 64: Single Test Screens

    MI 3360 OmegaPAT XA Single tests For the selected group a submenu with all single tests that belongs to the selected group and Area group is displayed. 6.1.1 Single test screens In the Single test screens measuring results, sub-results, limits and parameters of the measurement are displayed.
  • Page 65: Single Test Start Screen

    MI 3360 OmegaPAT XA Single tests 6.1.1.1 Single test start screen Single test start screen can be opened from Memory organizer or from Single test main menu. Figure 6.2: Single test start screen Options Starts the measurement. Opens help screens. Refer to chapter 6.1.3 Help screens for more information.
  • Page 66: Setting Parameters And Limits Of Single Tests

    MI 3360 OmegaPAT XA Single tests 6.1.1.2 Setting parameters and limits of single tests Figure 6.3: Screens in menu for setting Single test parameters and limits Options Selects parameter (white) or limit (red). Selects value of parameter or limit. In case of many (multiple pages of) parameters or limits: The scroll bar on the right side of screen can be used With right / left keys it can be jumped page up /...
  • Page 67: Single Test Screen During Test

    MI 3360 OmegaPAT XA Single tests 6.1.1.3 Single test screen during test Figure 6.4: Single test screen (during measurement) Options (during test) Stops the single test measurement. Proceeds to the next step of the measurement (if measurement consists of more steps).
  • Page 68: Single Test Result Screen

    MI 3360 OmegaPAT XA Single tests 6.1.1.4 Single test result screen Figure 6.5: Single test result screen Options (after measurement is finished) Starts a new measurement. Saves the result. A new measurement was selected and started from a Structure object in the structure tree: The measurement will be saved under the selected Structure object.
  • Page 69: Single Test Memory Screen

    MI 3360 OmegaPAT XA Single tests Opens screen for changing parameters and limits. Refer to chapter 6.1.1.2 Setting parameters and limits of single tests for more information. Enters cross selector. Refer to chapter 6.1 Selection modes for more information. long on 6.1.1.5 Single test memory screen Figure 6.6: Single test memory screen Options...
  • Page 70: Single Test (Inspection) Screens

    MI 3360 OmegaPAT XA Single tests 6.1.2 Single test (inspection) screens Visual and Functional inspections can be treated as a special class of tests. Items to be visually or functionally checked are displayed. In addition on-line statuses and other information are displayed.
  • Page 71: Single Test (Inspection) Screen During Test

    MI 3360 OmegaPAT XA Single tests Opens help screens. Refer to chapter 6.1.3 Help screens for more information. 6.1.2.2 Single test (Inspection) screen during test Figure 6.9: Inspection screen (during inspection) Options (during test) Selects item. Applies a pass to the selected item or group of items. Applies a fail to the selected item or group of items.
  • Page 72: Single Test (Inspection) Result Screen

    MI 3360 OmegaPAT XA Single tests Stops the inspection. Goes to the result screen. Rules for automatic applying of statuses:  The parent item(s) can automatically get a status on base of statuses in child items. the fail status has highest priority. A fail status for any item will result in a fail status in all parent items and an overall fail result.
  • Page 73: Single Test (Inspection) Memory Screen

    MI 3360 OmegaPAT XA Single tests A new inspection was started from the Single test main menu: Saving under the last selected Structure object will be offered by default. The user can select another Structure object or create a new Structure object. By pressing the key in Memory organizer menu the inspection is saved under selected location.
  • Page 74: Help Screens

    MI 3360 OmegaPAT XA Single tests 6.1.3 Help screens Help screens contain diagrams for proper connection of the instrument. Figure 6.12: Examples of help screens Options: Opens help screen. Goes to previous / next help screen.
  • Page 75: Single Test Measurements

    MI 3360 OmegaPAT XA Single tests 6.2 Single test measurements 6.2.1 Visual inspection Figure 6.13: Visual inspection menu Test circuit Figure 6.14: Visual inspection test circuit Visual inspection procedure  Select the appropriate Visual function.  Start the inspection.  Perform the visual inspection of the appliance / equipment.
  • Page 76: Continuity // Protective Earth Resistance

    MI 3360 OmegaPAT XA Single tests 6.2.2 Continuity // Protective earth resistance Figure 6.16: Continuity test // Protective earth resistance menu Test results / sub-results R ....Resistance Test parameters Output: [P/S – PE, MS_PE – IEC_PE] Output (Continuity) Output: [P/S – PE] Output (Protective earth resistance) Test current I out: [0.2 A, 10 A, 25 A]...
  • Page 77 MI 3360 OmegaPAT XA Single tests Figure 6.18: Continuity P/S – PE Figure 6.19: Protective Earth Resistance Continuity // Protective earth resistance measurement procedure  Select the Continuity // Protective Earth Resistance function.  Set test parameters / limits.  Connect device under test to the instrument (see test circuits above).
  • Page 78: Compensation Of Test Lead / Iec Test Cable Resistance

    MI 3360 OmegaPAT XA Single tests Figure 6.20: Example of Continuity and Protective Earth Resistance measurement results 6.2.2.1 Compensation of test lead / IEC test cable resistance This chapter describes how to compensate the test leads resistance in Continuity (Output = P/S –...
  • Page 79: Flash Test

    MI 3360 OmegaPAT XA Single tests Figure 6.22: Result with old and new calibration values Note: The calibration value is correct only for the output (P/S terminal – PE terminal on test socket)  at which the calibration was carried out. 6.2.3 Flash test Figure 6.23: Flash test menu Test results / sub-results...
  • Page 80 MI 3360 OmegaPAT XA Single tests Test circuits Figure 6.24: Flash test 1500 V Figure 6.25: Flash test 3000 V Flash measurement procedure  Select the Flash function.  Set test parameters / limits.  Connect device under test to the instrument (see test circuits above). ...
  • Page 81: Insulation Resistance (Riso, Riso-S)

    MI 3360 OmegaPAT XA Single tests 6.2.4 Insulation resistance (Riso, Riso-S) Figure 6.27: Insulation resistance test menus Test results / sub-results Riso ... Insulation resistance Riso-S ..Insulation resistance-S Um..... Test voltage Test parameters Type of test Type [Riso, Riso-S, (Riso, Riso-S)] Nominal test voltage Uiso [250 V, 500 V] Duration [Off, 2 s …...
  • Page 82: Sub-Leakage (Isub, Isub-S)

    MI 3360 OmegaPAT XA Single tests Figure 6.30: Insulation resistance measurement with probe Riso-S (socket – P/S) Insulation resistance measurement procedure  Select the R iso function.  Set test parameters / limits.  Connect device under test to the instrument (see test circuits above). ...
  • Page 83 MI 3360 OmegaPAT XA Single tests Test parameters Type of test Type [Isub, Isub-S, (Isub, Isub-S)] Output voltage Output [230 V]ac Duration [Off, 2 s … 180 s] Duration Test limits H Limit(Isub) [Off, 0.25 mA … 15.0 mA, Custom] Limit (Isub) H Limit(Isub-S) [Off, 0.25 mA …...
  • Page 84: Differential Leakage

    MI 3360 OmegaPAT XA Single tests Sub-leakage measurement procedure  Select the Sub-leakage function.  Set test parameters / limits.  Connect device under test to the instrument (see test circuits above).  Start measurement.  Measurement can be stopped manually or by timer. ...
  • Page 85 MI 3360 OmegaPAT XA Single tests Test parameters Duration [Off, 2 s … 180 s] Duration Change status Change [YES, NO] YES: The instrument measures leakage current in two sequential steps with delay* in between. The phase voltage is firstly applied to the right live output of the mains test socket and secondly to the left live output of the mains test socket.
  • Page 86: Ipe Leakage

    MI 3360 OmegaPAT XA Single tests 6.2.7 Ipe Leakage Figure 6.40: Ipe Leakage test menu Test results / sub-results Ipe ..... PE current P ....Power Test parameters Duration [Off, 2 s … 180 s] Duration Change status Change [YES, NO] YES: The instrument measures leakage current in two sequential steps with delay* in between.
  • Page 87: Touch Leakage

    MI 3360 OmegaPAT XA Single tests  Save results (optional). Figure 6.42: Examples of Ipe Leakage measurement results 6.2.8 Touch Leakage Figure 6.43: Touch Leakage test menu Test results / sub-results Itou .... Touch Leakage current P ....Power Test parameters Duration [Off, 2 s …...
  • Page 88 MI 3360 OmegaPAT XA Single tests Test circuit Figure 6.44: Touch Leakage Touch Leakage measurement procedure  Select the Touch Leakage function.  Set test parameters / limits.  Connect device under test to the instrument (see test circuit above). ...
  • Page 89: Power

    MI 3360 OmegaPAT XA Single tests 6.2.9 Power Figure 6.46: Power measurement menu Test results / sub-results P ....Active power S ....Apparent power Q ....Reactive power PF ....Power factor THDu ..Total harmonic distortion – voltage THDi ..
  • Page 90: Leak's & Power

    MI 3360 OmegaPAT XA Single tests  Save results (optional). Figure 6.48: Examples of Power measurement results 6.2.10 Leak's & Power Figure 6.49: Leak’s & Power measurement menu Test results / sub-results P ....Active power Itou .... Touch Leakage current Idiff ....
  • Page 91: Prcd Test

    MI 3360 OmegaPAT XA Single tests Test limits H Limit(P) [Off, 10 W … 3.50 kW, Custom] High Limit (P) L Limit(P) [Off, 10 W … 3.50 kW, Custom] Low Limit (P) H Limit(Idiff) [Off, 0.25 mA … 15.0 mA, Custom] High Limit (Idiff) H Limit(Itou) [Off, 0.25 mA …...
  • Page 92 MI 3360 OmegaPAT XA Single tests Test results / sub-results t ∆N ……trip out time t I∆N x1, (+) ……trip-out time (I , (+) positive polarity)  N t I∆N x1, (-) ……trip-out time (I , (-) negative polarity)  N t I∆N x5, (+) ……trip-out time (I...
  • Page 93: Rcd Test

    MI 3360 OmegaPAT XA Single tests Figure 6.54: Examples of PRCD measurement results 6.2.12 RCD test Figure 6.55: RCD measurement menu Test results / sub-results t ∆N ……trip out time t I∆N x1, (+) ……trip-out time (I , (+) positive polarity) ...
  • Page 94 MI 3360 OmegaPAT XA Single tests Test limits Test limits for Pass / Fail statuses are set automatically, depending on set parameters. Test circuit Figure 6.56: RCD test RCD measurement procedure  Connect the instrument to the circuit with RCD (see test circuit above). ...
  • Page 95: Pe Conductor (Prcd)

    MI 3360 OmegaPAT XA Single tests 6.2.13 PE conductor (PRCD) Figure 6.58: PE conductor (PRCD) test menu Test results / sub-results R ....Resistance Result…….Indication that the protection of the varistor in PE connection works properly Test parameters Type of PRCD Design [2 pole, 3 pole, K/Di (varistor), S (3 pole)] Duration [Off, 2 s …...
  • Page 96: Open Conductor (Prcd)

    MI 3360 OmegaPAT XA Single tests  Save results (optional). Figure 6.60: Examples of PE conductor (PRCD) results Note: Mains voltage is applied to the PRCD during the test.  The instrument uses different test methods in regard to the set PRCD type. For 2 pole, 3 ...
  • Page 97: Prcd Pe Probe Test

    MI 3360 OmegaPAT XA Single tests Test circuit Figure 6.62: Open conductor (PRCD) test Open conductor (PRCD) measurement procedure  Select the Open Conductor (PRCD) function.  Set test parameters.  Connect the PRCD to the instrument (see test circuit above). ...
  • Page 98 MI 3360 OmegaPAT XA Single tests Test results / sub-results Result…….Indication of the test [Pass, Fail] Test parameters / limits Test mode Test [manual, auto] Type of PRCD Design [2 pole, 3 pole, K/Di (varistor), S (3 pole)] Test circuits Figure 6.65: PRCD PE probe test (manual) Figure 6.66: PRCD PE probe test (auto) PRCD PE probe test measurement procedure (Test = manual)
  • Page 99: Polarity

    MI 3360 OmegaPAT XA Single tests PRCD PE probe test measurement procedure (Test = auto)  Select the PRCD PE probe test function.  Set test parameters (Test = auto)  Connect the PRCD to be tested to the instrument (see test circuits above). ...
  • Page 100 MI 3360 OmegaPAT XA Single tests Test circuits Figure 6.69: Polarity test (manual) Figure 6.70: Polarity test (auto) Polarity measurement procedure (Mode = normal)  Select the Polarity function.  Set test parameters (Mode = normal).  Connect the cable to be tested to the instrument (see test circuits above). ...
  • Page 101: Clamp Current

    MI 3360 OmegaPAT XA Single tests Figure 6.71: Examples of Polarity test Note:  Active polarity test is intended for testing cords equipped with (P)RCD or mains operated switches. 6.2.17 Clamp current Figure 6.72: Clamp current test menu Test results / sub-results I ....
  • Page 102 MI 3360 OmegaPAT XA Single tests Test circuit Figure 6.73: Clamp current Clamp current measurement procedure  Select the Clamp current function.  Set test parameters / limits.  Connect the current clamp to the instrument.  Embrace wire(s) that has to be measured with current clamp (see test circuits above). ...
  • Page 103: Insulation Resistance - Riso (Welding Equipment)

    *For more information refer to chapter Measurements according to IEC/ EN 60974-4 – Insulation resistance in 3-phase adapter user manual. Figure 6.76: Examples of Insulation resistance (welding equipment) measurement results Note:  This test is applicable only with connected METREL 3-phase adapter (A1422).
  • Page 104: Welding Circuit Leakage - I Leak (W-Pe)

    Test circuit, I leak (W-PE) measurement procedure  Select the I leak (W-PE) function.  Set test parameters / limits.  Connect METREL 3-phase adapter (A 1422) to the instrument*.  Connect device under test to the 3-phase adapter*.  Start measurement. ...
  • Page 105: Primary Leakage

    Single tests Figure 6.78: Examples of Ileak W-PE Leakage measurement results Note:  This test is applicable only with connected METREL 3-phase adapter (A1422). 6.2.20 Primary Leakage Figure 6.79: Primary Leakage menu Test results / sub-results Idiff .... Primary leakage current Test parameters Duration [Off, 2 s …...
  • Page 106: No-Load Voltage

    Leakage current in 3-phase adapter user manual. Figure 6.80: Examples of Ileak W-PE Leakage measurement results Notes:  This test is applicable only with connected METREL 3-phase adapter (A1422).  The differential current measurement principle is used for this test. 6.2.21 No-load voltage Figure 6.81: No-load voltage menu...
  • Page 107: Insulation Resistance - Riso (Medical Equipment)

    3-phase adapter user manual. Figure 6.82: Examples of No-load voltage measurement results Note:  This test is applicable only with connected METREL 3-phase adapter (A1422). 6.2.22 Insulation resistance – Riso (medical equipment) Figure 6.83: Insulation resistance (medical equipment) test menus...
  • Page 108 MI 3360 OmegaPAT XA Single tests Test results / sub-results Riso ... Insulation resistance Um..... Test voltage Test parameters Test Test_Riso_ME [LN-PE, LN-P/S, LN-AP, PE-AP] Duration [Off, 2 s … 180 s] Duration Nominal test voltage Uiso [500 V] Test limit Limit(Riso) [Off, 2 MΩ...
  • Page 109 MI 3360 OmegaPAT XA Single tests Test circuits Figure 6.84: Insulation resistance – LN-PE Figure 6.85: Insulation resistance – LN-P/S Figure 6.86: Insulation resistance – LN-AP Figure 6.87: Insulation resistance – PE-AP...
  • Page 110: Equipment Leakage (Medical Equipment)

    MI 3360 OmegaPAT XA Single tests RISO measurement procedure  Select the Riso function.  Set test parameters / limits.  Connect device under test to the instrument (see test circuits above).  Start measurement.  Measurement can be stopped manually or by timer. ...
  • Page 111 MI 3360 OmegaPAT XA Single tests Unom [100 V … 240 V] Nominal line to earth voltage whose value corresponds to the nominal mains voltage Test limits Limit(Ieq) [Off, 500 µA, 1000 µA] Limit (Ieq) (alternative) Limit(Ieq) [Off, 100 µA, 500 µA] Limit (Ieq) (direct, differential) Test circuits Figure 6.90: Equipment Leakage (alternative) on Class I ME...
  • Page 112 MI 3360 OmegaPAT XA Single tests Figure 6.93: Equipment Leakage (differential) on Class I ME Figure 6.94: Equipment Leakage (direct, differential) on Class II ME Equipment Leakage measurement procedure  Select the Equipment Leakage function.  Set test parameters / limits. ...
  • Page 113: Applied Part Leakage (Medical Equipment)

    MI 3360 OmegaPAT XA Single tests 6.2.24 Applied Part Leakage (medical equipment) Figure 6.96: Applied part leakage measurement menu Test results / sub-results Iap………...Applied part leakage current Uap……….Voltage between applied part and earth during measurement P ....Active power Test parameters Duration [Off, 2 s …...
  • Page 114 MI 3360 OmegaPAT XA Single tests Test circuit Figure 6.97: Applied part leakage (alternative) on Class I ME Figure 6.98: Applied part leakage (alternative) on Class II ME Figure 6.99: Applied part leakage (direct) on Class I ME Figure 6.100: Applied part leakage (direct) on Class II ME...
  • Page 115: Touch Current (Medical Equipment)

    MI 3360 OmegaPAT XA Single tests Applied part leakage measurement procedure  Select the Applied part leakage function.  Set test parameters / limits.  Connect device under test to the instrument (see test circuits above).  Start measurement.  Measurement can be stopped manually or by timer.
  • Page 116 MI 3360 OmegaPAT XA Single tests Unom [100 V … 240 V]. Nominal line to earth voltage whose value corresponds to the nominal mains voltage Test limits Limit(Itou) [Off, 100 µA] Limit (Itou) Test circuit Figure 6.103: Touch current Applied part leakage measurement procedure ...
  • Page 117: Functional Test

    MI 3360 OmegaPAT XA Single tests 6.2.26 Functional test Figure 6.105: Functional test menu Test parameters (optional) For the optional Power measurement the parameters and limits are the same as set in Power test. Test circuit Figure 6.106: Functional test Functional test inspection procedure ...
  • Page 118: Auto Sequences

    The results of an Auto sequence® can be stored in the memory together with all related information. Auto Sequences® can be pre-programmed on PC with the Metrel ES Manager software and uploaded to the instrument. On the instrument parameters and limits of individual single test in the Auto Sequence®...
  • Page 119: Searching In Auto Sequences® Menu

    MI 3360 OmegaPAT XA Auto Sequences® New Auto Sequence® group is selected and all  Auto Sequences® within that group are displayed on the screen. 7.1.2 Searching in Auto Sequences® menu In Auto Sequence® menu it is possible to search for Auto Sequences® on base of their Name or Short code.
  • Page 120 MI 3360 OmegaPAT XA Auto Sequences® Clears all filters. Sets filters to default value.  Clear filters Searches through the active Auto Sequence®  group according filters. The results are shown in the Search results Search screen presented on Figure 7.1 and Figure 7.2. Figure 7.1: Search results screen –...
  • Page 121: Organization Of Auto Sequences® In Auto Sequences® Menu

    MI 3360 OmegaPAT XA Auto Sequences® Goes to Auto Sequence® view menu. Starts the selected Auto Sequence®. 7.1.3 Organization of Auto Sequences® in Auto Sequences® menu The Auto Sequences® to be carried out can be selected from the Main Auto Sequences® menu.
  • Page 122: Organization Of An Auto Sequence

    MI 3360 OmegaPAT XA Auto Sequences® 7.2 Organization of an Auto Sequence® An Auto Sequence® is divided into three phases:  Before starting the first test the Auto Sequence® view menu is shown (unless it was started directly from the Main Auto Sequences® menu). Parameters and limits of individual measurements can be set in this menu.
  • Page 123: Auto Sequence® View Menu (Measurement Is Selected)

    MI 3360 OmegaPAT XA Auto Sequences® 7.2.1.2 Auto Sequence® view menu (measurement is selected) Figure 7.5: Auto Sequence® view menu – measurement selected Options: Selects single test. Opens menu for changing parameters and limits of selected measurements. Refer to chapter 6.1.1.2 Setting parameters and limits of single tests more...
  • Page 124: Indication Of Loops

    MI 3360 OmegaPAT XA Auto Sequences® Sets operation mode for multiple points. For more information see chapter 7.2.1.4 Managing multiple points. 7.2.1.3 Indication of Loops The attached ‘x3’ at the end of single test name indicates that a loop of single tests is programmed.
  • Page 125 MI 3360 OmegaPAT XA Auto Sequences® Figure 7.6: Auto Sequence® – Example of a pause with message Figure 7.7: Auto Sequence® – Example of a finished measurement with options for proceeding Options (during execution of an Auto Sequence®): Proceeds to the next step in the test sequence. Repeats the measurement.
  • Page 126: Auto Sequence® Result Screen

    For more information about programming Auto Sequences® refer to chapter Appendix E Programming of Auto Sequences® on Metrel ES Manager.  If Inspection Expert mode flow command is set, the visual inspection screen and Functional inspection screen are displayed for 1 second and an overall PASS is automatically applied at the end of test.
  • Page 127 MI 3360 OmegaPAT XA Auto Sequences® Saves the Auto Sequence® results. A new Auto Sequence® was selected and started from a Structure object in the structure tree:  The Auto Sequence® result will be saved under the selected Structure object. A new Auto Sequence®...
  • Page 128: Auto Sequence® Memory Screen

    MI 3360 OmegaPAT XA Auto Sequences® Figure 7.9: Details of menu for viewing details of Auto Sequence® results Options (menu for viewing details of Auto Sequence® results): Details of selected single test in Auto Sequence® are displayed. View parameters and limits of selected single test. Add comment to selected single test results.
  • Page 129: Print Label Menu

    MI 3360 OmegaPAT XA Auto Sequences® ® Write RFID / NFC tag. All data including Auto Sequence results are written to the RFID / NFC writing device. Refer to Appendix C - Print labels and write / read RFID / NFC tags for supported tag types. Note: ...
  • Page 130: Maintenance

    MI 3360 OmegaPAT XA Maintenance 8 Maintenance 8.1 Periodic calibration It is essential that all measuring instruments are regularly calibrated in order for the technical specification listed in this manual to be guaranteed. We recommend an annual calibration. 8.2 Fuses There are two fuses on the left side panel: F1, F2: T 16 A / 250 V / (32 ...
  • Page 131: Communications

    Tree structure and Auto Sequences® from Metrel ES Manager PC software can be uploaded to the instrument. Metrel ES Manager is a PC software running on Windows 7, Windows 8, Windows 8.1 and Windows 10. There are three communication interfaces available on the instrument: RS-232, USB and Bluetooth.
  • Page 132: Bluetooth Communication With Printers And Scanners

    Some Android applications automatically carry out the setup of a Bluetooth connection.  It is preferred to use this option if it exists. This option is supported by Metrel's Android applications. If this option is not supported by the selected Android application then configure a ...
  • Page 133: Test Adapter (A 1474)

     See 3-phase adapter user manual for more details.  Do not connect other devices than Metrel test adapters to the 3 PHASE ADAPTER connector. 9.5.2 110 V Test Adapter (A 1474) 110 V Adapter (A 1474) is used as interface to connect 110 V appliances to the instrument.
  • Page 134: Technical Specifications

    MI 3360 OmegaPAT XA Technical specifications 10 Technical specifications 10.1 Continuity // Protective earth resistance Continuity Range Resolution Accuracy 0.00  … 19.99  0.01  (2 % of reading + 2 D) 20.0  … 99.9  0.1  ...
  • Page 135: Sub-Leakage Current, Substitute Leakage Current - S

    MI 3360 OmegaPAT XA Technical specifications 10.3 Sub-Leakage Current, Substitute Leakage Current - S Substitute leakage current, Substitute leakage current - S Range Resolution Accuracy (3 % of reading + 3 D) 0.00 mA … 1.99 mA 0.01 mA Isub (5 % of reading) 2.00 mA …...
  • Page 136: Touch Leakage Current

    MI 3360 OmegaPAT XA Technical specifications Operating range (acc. to EN 61557-16) ... 0.010 mA … 19.99 mA Test terminals: Socket L,N – Socket PE Socket L – Socket N 10.6 Touch leakage current Touch leakage current Range Resolution Accuracy (3 % of reading + 3 D) 0.000 mA …...
  • Page 137: Leak's & Power

    MI 3360 OmegaPAT XA Technical specifications Total Harmonic Distortion (voltage) Range Resolution Accuracy (5 % of reading + 5 D) 0.0 % … 99.9 % THDU 0.1 % Total Harmonic Distortion (current) Range Resolution Accuracy 0.00 A … 16.00 A (3 % of reading + 5 D) 0.01 A THDI...
  • Page 138 MI 3360 OmegaPAT XA Technical specifications Power (apparent) Range Resolution Accuracy 0 VA … 999 VA (5 % of reading + 5 D) 1 VA  5 % of reading 1.00 kVA … 3.70 kVA 10 VA Power (reactive) Range Resolution Accuracy 0 VAr …...
  • Page 139: Prcd Test

    MI 3360 OmegaPAT XA Technical specifications 10.9 PRCD test Trip-out time Range Resolution Accuracy  3 ms 0 ms … 300 ms (999 ms*) (½I ) 1 ms N  3 ms tΔN 0 ms … 300 ms (I 1 ms N ...
  • Page 140: Pe Conductor (Prcd)

    MI 3360 OmegaPAT XA Technical specifications 10.11 PE conductor (PRCD) PE conductor (Type = 2 pole, 3 pole, S(3 pole)) Range Resolution Accuracy 0.00  … 19.99  0.01  (2 % of reading + 2 D) 20.0  … 99.9  0.1 ...
  • Page 141: Polarity

    MI 3360 OmegaPAT XA Technical specifications Test terminals: Result (manual) Socket, P/S Socket – IEC, P/S Result (auto) 10.14 Polarity Test voltage (normal) ..............< 50 V Test voltage (active)…………………………………………..mains voltage Power consumption of tested device during the active test…….< 25 VA Test terminals: Socket –...
  • Page 142: Insulation Resistance Riso (Welding Equipment)

    MI 3360 OmegaPAT XA Technical specifications 10.17 Insulation resistance Riso (welding equipment) Riso Range Resolution Accuracy (3 % of reading + 2 D) 0.00 M … 19.99 M 0.01 M  5 % of reading 20.0 M … 99.9 M Riso 0.1 M...
  • Page 143: Insulation Resistance (Medical Equipment)

    MI 3360 OmegaPAT XA Technical specifications 10.21 Insulation Resistance (medical equipment) Riso Range Resolution Accuracy (3 % of reading + 2 D) 0.00 M … 19.99 M 0.01 M Riso  5 % of reading 20.0 M … 199.9 M 0.1 M...
  • Page 144: Applied Part Leakage

    MI 3360 OmegaPAT XA Technical specifications 10.23 Applied Part leakage Applied Part leakage current (direct, alternative) Range Resolution Accuracy 0.000 mA … 1.999 mA 1 µA (3 % of reading + 3 D) 2.00 mA … 19.99 mA (5 % of reading) 0.01 mA Uap (direct, alternative) Range...
  • Page 145: General Data

    MI 3360 OmegaPAT XA Technical specifications 10.25 General data Mains supply Supply voltage, frequency ....... 110 V / 230 V AC, 50 Hz / 60 Hz Supply voltage tolerance ......10 % Max. power consumption......300 VA (without load on test socket) Max.
  • Page 146: Appendix A Structure Objects In Omegapat Xa

    MI 3360 OmegaPAT XA Appendix A Appendix A Structure objects in OmegaPAT XA Structure elements used in Memory Organizer are instrument’s Profile dependent. Symbol Default name Description Node Node Project Project Location Location Client Client Appliance Appliance (basic description) Appliance FD Appliance (full description) Medical device Medical device (basic description)
  • Page 147: Appendix B Profile Notes

    MI 3360 OmegaPAT XA Appendix B Appendix B Profile Notes There are no specific profile notes for OmegaPAT XA MI 3360.
  • Page 148: Appendix C Print Labels And Write / Read Rfid / Nfc Tags

    – barcode or QR code – in addition. The instrument supports RFID / NFC reader / writer device; tag type supported is NTAG216. Please check with Metrel or distributor which printers and labels are supported in your OmegaPAT XA instrument.
  • Page 149 MI 3360 OmegaPAT XA Appendix C Label Form size Tag content Data1 label Data 2 label type W x H arrangement (mm) Classic Barcode Test code, appliance ID Appliance ID Text Test code, appliance ID, Appliance ID, test or test or retest date, status, retest date, status, user user Test code, appliance ID,...
  • Page 150: Generic Tag Format

    MI 3360 OmegaPAT XA Appendix C  Test or Retest date: is set in the General Settings => Devices => Writing devices menu.  If Auto Sequence® was modified, its short code is marked with asterisk (*). Following table describes data content written on RFID / NFC tag. RFID / NFC tag type Data NTAG216...
  • Page 151 MI 3360 OmegaPAT XA Appendix C Notes:  Data not available will not be printed on the label.  Object without appended Auto Sequence® test has no status!  If Auto Sequence® was modified, its short code is marked with asterisk (*). ...
  • Page 152: Appendix D Default List Of Auto Sequences

    MI 3360 OmegaPAT XA Appendix D Appendix D Default list of Auto Sequences® Default list of Auto Sequences® for MI 3360 OmegaPAT XA instrument is available on Metrel home page: http://www.metrel.si...
  • Page 153: Appendix E Programming Of Auto Sequences® On Metrel Es Manager

    Programming of Auto Sequences® Appendix E on Metrel ES Manager The Auto Sequence® editor is a part of the Metrel ES Manager software. In Auto Sequence® editor Auto Sequence® can be pre-programmed and organized in groups, before uploaded to the instrument.
  • Page 154: Managing Groups Of Auto Sequences

    MI 3360 OmegaPAT XA Appendix E appropriate Single tests (measurements, inspections and custom inspections) and Flow commands and setting their parameters, arbitrary Auto Sequences® can be created. Figure E.2: Example of an Auto Sequence® header Figure E.3: Example of a measurement step Figure E.4: Example of an Auto Sequence®...
  • Page 155 MI 3360 OmegaPAT XA Appendix E Operation options on Group of Auto Sequences® are available from menu bar at the top of Auto Sequence® Editor workspace. File operation options: Opens a file (Group of Auto Sequences®). Creates a new file (Group of Auto Sequences®). Saves / Saves as the opened Group of Auto Sequences®...
  • Page 156: Auto Sequence® Name, Description And Image Editing

    MI 3360 OmegaPAT XA Appendix E Double click on the object name allows it name edit: Auto Sequence® name: Edit Auto Sequence® name DOUBLE CLICK Folder name: Edit folder name Drag and drop of the selected Auto Sequence® or Folder / Subfolder moves it to a new location: “Drag and drop”...
  • Page 157: Search Within Selected Auto Sequence® Group

    MI 3360 OmegaPAT XA Appendix E E.2.2 Search within selected Auto Sequence® group When function is selected, Search menu as presented on Figure E.7 appear on the screen. By entering the text into search box, found results are automatically highlighted with yellow background.
  • Page 158: Elements Of An Auto Sequence

    Result step. E.3.2 Single tests Single tests are the same as in Metrel ES Manager Measurement menu. Limits and parameters of the measurements can be set. Results and sub-results can’t be set. E.3.3 Flow commands Flow commands are used to control the flow of measurements.
  • Page 159: Description Of Flow Commands

    MI 3360 OmegaPAT XA Appendix E By a double click on the element. Viewing / changing parameters of flow commands or single tests. Setting number of measurement By setting a number in the field. step repetitions Right click on the selected measurement step / flow command: Copy –...
  • Page 160 MI 3360 OmegaPAT XA Appendix E No notifications mode Instrument skips pre-test warnings (see chapter 4.5 Symbols and messages for more information). Parameters On – enables No notifications mode State Off – disables No notifications mode Appliance info Instrument enables to automatically select the appliance type and add the Appliance ID, Appliance name and Retest period to the Auto Sequence®.
  • Page 161 MI 3360 OmegaPAT XA Appendix E On – enables automatic settings of tickers in Visual and Functional tests. State Off – disables automatic settings of tickers in Visual and Functional tests. Operation after end of test This flow command controls the proceeding of the Auto Sequence® in regard to the measurement results.
  • Page 162: Custom Inspections Programming

    MI 3360 OmegaPAT XA Appendix E E.6 Custom Inspections programming Arbitrary set of tasks dedicated to specific user defined Inspections can be programmed with application of Custom Inspection Editor Tool, accessible from Auto Sequence® Editor workspace. Custom Inspections are stored in dedicated file *.indf with user defined name. For application of Custom Inspections as a single test within Auto Sequence®...
  • Page 163 MI 3360 OmegaPAT XA Appendix E Add New Custom Inspection. New inspection with default name Custom Inspection and default scope Visual appear on the editor workspace. It contains one Item task with default name Custom Inspection and default Type Pass_Fail_Checked_Empty. Default Name and Type can be edited –...
  • Page 164: Applying Custom Inspections

    E.6.2 Applying Custom Inspections Custom inspections can be applied in Auto Sequences®. Direct assignment of Custom inspection to the Metrel ES manager structure objects is not possible. After custom created Inspection Data file is opened, available inspections are listed in Custom Inspections tab of Single test area of Auto Sequence®...

Table of Contents