Installation Environment
2.3.1 Locational Requirements
Environments with high-temperature, dust, harmful gases, unstable voltage, big vibration,
high noise or exposed to flammable, explosive, electromagnetic interference (large radar
station, transmitting station, transformer substation) are not suitable for the operation of
mBS1100, and thus should be avoided. Places prone to have impounded water, soaking,
leakage, or condensation, should also be avoided.
In the construction process, factors like climate, hydrology, geology, earthquake, electric
power, and transportation should be taken into consideration so that a proper location can
be chosen to meet the communication engineering environmental requirements, as well
as the technical requirements of network planning and communication equipment.
2.3.2 Environmental Requirements
Table 2-2 gives the base station's environmental requirements on temperature, humidity,
and voltage.
Table 2-2 Environmental Requirements of the Base Station
Item
Humidity
Relative humidity
(no
condensation)
Safety voltage
Range
-40℃~ 55℃
0% ~ 100%
42V ~ 58V
Typical value
25℃
5% ~ 95%
48V