Panel Mounting

The controller enclosure is constructed of a plastic base plate
and a plastic factory-snap-on cover.
NOTE: The controller is designed so that the cover does not
need to be removed from the base plate for either
mounting or wiring.
The controller mounts using four screws inserted through the
corners of the base plate. Fasten securely with four No. 6 or
No. 8 machine or sheet metal screws.
The controller can be mounted in any orientation. Ventilation
openings are designed into the cover to allow proper heat
dissipation, regardless of the mounting orientation.
DIN Rail Mounting (PUB6438S and PVB6438NS)
To mount the PUB6438S or PVB6438NS controller on a DIN
rail [standard EN50022; 1-3/8 in. x 9/32 in. (7.5 mm x 35 mm)],
refer to Fig. 6 and perform the following steps:
1. Holding the controller with its top tilted in towards the
DIN rail, hook the two top tabs on the back of the con-
troller onto the top of the DIN rail.
2. Push down and in to snap the two bottom flex connec-
tors of the controller onto the DIN rail.
IMPORTANT
To remove the controller from the DIN rail, perform
the following:
1. Push straight up from the bottom to release the top
tabs.
2. Rotate the top of the controller out towards you and
pull the controller down and away from the DIN rail to
release the bottom flex connectors.
62-0310—01
PANEL MOUNTING HOLE
(4X) 29/64 IN. (12)
PVB6438NS
2 2 2 2 2 2 2 2 3
2
3
3
1 2 3 4 5 6 7 8 0
9
1 2 3 4 5 6 7 8 0
5-3/64
(128)
1 1 1 1 1 1 1 1 2
1
1 2 3 4 5 6 7 8
9
0
1
2 3 4 5 6 7 8 0
6-29/64 (164)
6-27/32 (174)
CONTROLLER CAN BE MOUNTED IN ANY ORIENTATION.
3
3
3
3
3
3 4
3
9
5-3/64
(128)
5-29/64
(139)
1
9
1 2 3 4 5 6 7 8
DEPTH IS
2-1/4 (57)
TOP TABS
BOTTOM FLEX
CONNECTORS
Fig. 6. Controller DIN rail mounting (models PUB6438S
Piping (PVB6436AS and PVB6438NS)
Air flow Pickup
For PVB6436AS and PVB6438NS, connect the air flow pickup
to the two restrictor ports on the controller (see Fig. 7).
NOTES:
Use 1/4 inch (6 mm) outside diameter, with a
0.040 in. (1 mm) wall thickness, plenum-rated
1219 FR (94V-2) tubing.
Always use a fresh cut on the end of the tubing
that connects to the air flow pickups and the
restrictor ports on the controller.
Connect the high pressure or upstream tube to the plastic
restrictor port labeled (
stream tube to the restrictor port labeled (
Fig. 7. When twin tubing is used from the pickup, split the
pickup tubing a short length to accommodate the connections.
NOTES:
If controllers are mounted in unusually dusty or dirty
environments, an inline, 5-micron disposable air
filter (use 5-micron filters compatible with
4
PUB6438S
2 2 2 2 2 2 2 2 3
2
3
3
3
3
3
3
3
3 4
3
1 2 3 4 5 6 7 8 0
9
1 2 3 4 5 6 7 8 0
9
1 1 1 1 1 1 1 1 2
1
1
9
0
1
2 3 4 5 6 7 8 0
9
6-29/64 (164)
6-27/32 (174)
M29330
and PVB6438NS).
+