GENERAL INSTALLATION
The installation of EverWarm Film begins with planning a layout for the
Heating Film. This helps the installer understand how much Heating Film will
be needed, and which (and how many) Wiring Harnesses, Jumpers, Adders,
and extra Edge Sealing Tape might be needed. Additionally, a pre-planned
layout will determine thermostat (and possibly slave thermostat) locations.
FIRST, DETERMINE THE NUMBER OF S QUARE FEET OF HEATING FILM THAT
ARE REQUIRED FOR THE INSTALLATION. THIS WILL HELP TO DETERMINE
THE VOLTAGE NEEDED FOR THE INSTALLATION.
The Heating Film is capable of running on 120 volts or 240 volts. Installations
using 120 volts are limited to 100 square feet of Heating Film per dedicated
15 amp circuit. Installations using 240 volts are capable of a maximum 200
square feet of Heating Film per a dedicated 15 amp circuit. Each circuit can
be controlled individually by using a standard individual thermostat for
complete zone control, or up to ten circuits (maximum 2000 sq-ft) may be
controlled from one master thermostat.
EXAMPLE OF A
400 SQ-FT SYSTEM.
Qty 1 Master thermostat
Qty 2 Slave units
Qty 1 JP-60 (60" Jumper)
Qty 2 A-240 Adder
Qty 1 J-240 Harness
Qty 1 J3-240 Harness
S E C T I O N 5
S E C T I O N 5
1
PAGE 24
INSTRUCTIONS

LAYOUT

A-240
ADDER
A-240
ADDER
JUMPER
EverWarm Radiant Floors
J3-240
HARNESS
SLAVE 2
SLAVE 1
THERMOSTAT
J-240
HARNESS