Deactivating Grounding Conductor Monitoring; Configuring The Energy Meter - SMA SUNNY BOY 1.5 Operating Manual

Hide thumbs Also See for SUNNY BOY 1.5:
Table of Contents

Advertisement

9 Configuration of the Inverter
The basic procedure for changing operating parameters is explained in another section (see
Section 9.1 "Changing Operating Parameters", page 51).
Parameters
Application ID
GOOSE-Mac address 01:0C:CD:01:00:00 to
Procedure:
1. Select the parameter group External communication > IEC 61850 configuration.
2. In the field Application ID, enter the application ID of the grid operator gateway. You will
receive this value from your grid operator. You can enter a value between 0 and 16384. The
value 16384 indicates "deactivated".
3. In the field GOOSE-Mac address, enter the MAC address of the grid operator gateway
from which the inverter is to receive the control commands. You will receive this value from
your grid operator.
☑ The receipt of control signals from the grid operator is activated.

9.11 Deactivating Grounding Conductor Monitoring

If the inverter is to be installed in an IT network or another grid configuration in which deactivation
of the grounding conductor monitoring is required, deactivate the grounding conductor monitoring
as follows.
The basic procedure for changing operating parameters is explained in another section (see
Section 9.1 "Changing Operating Parameters", page 51).
Procedure:
• In the parameter group Grid monitoring > Grid monitoring > Country standard set the
parameter PE connection monitoring to Off.

9.12 Configuring the Energy Meter

You can add an energy meter to your PV system or replace an existing energy meter.
The basic procedure for changing operating parameters is explained in another section (see
Section 9.1 "Changing Operating Parameters", page 51).
56
SB15-25-1VL-40-BE-en-11
Value/range
0 to 16384
01:0C:CD:01:02:00
SMA Solar Technology AG
Resolution
Default
1
16384
1
01:0C:CD:01:00:00
Operating Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunny boy 2.5

Table of Contents