Automatic Initialization Of Linear Actuators - Siemens SIPART PS2 6DR5 series Operating Instructions Manual

Electropneumatic positioners
Hide thumbs Also See for SIPART PS2 6DR5 series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Stroke [mm]
5 to 20
25 to 35
40 to 130
1. Move the carrier pin on the lever. Select the scale position equal to the nominal stroke or a next-higher position.
2. Tighten the carrier pin using the M6 hexagon nut.
Connecting the positioner
1. Connect a suitable current or voltage source. The positioner is now in the "P manual mode". The current potentiometer
voltage (P) in percent is shown in the upper line of the display, e.g.: "P12.3", and "NOINI" blinks in the lower line:
2. Connect the actuator and the positioner to the pneumatic lines.
3. Supply the pneumatic auxiliary power to the positioner.
Setting the actuator
1. Check whether the mechanical unit can be moved freely in the entire actuating range. Move the drive to the respective
end position for this purpose using the
Note
End position
By simultaneously pressing the
2. Now move the actuator to the horizontal position of the lever.
3. A value between "P48.0" and "P52.0" is shown on the display.
4. If a value beyond this value range is shown on the display, you must move the friction clutch. Move the friction clutch
until a value between "P48.0" and "P52.0" is achieved. The closer this value is to "P50.0", the more accurately the
positioner determines the stroke travel.
Note
The following is applicable for the flameproof enclosure version:
The inner friction clutch is fixed. Therefore, only move the outer friction clutch.
5.6.2

Automatic initialization of linear actuators

Conditions
The following conditions must be fulfilled before activating the automatic initialization:
1. The actuator spindle can be moved completely.
2. The actuator spindle is at a central position after moving.
Initializing the positioner automatically
Note
Interrupting initialization
An ongoing initialization can be interrupted at any time. To do this, press the
are retained.
All parameters are reset to factory settings only if you have explicitly activated the preset settings in the "PRST" parameter.
28
Lever
Short
Short
Long
or
and
buttons, you reach the end position faster.
Position of the transmission ratio selector
In [°]
33
90
90
button.
Position
Down
Up
Up
button. The settings configured until then
SIPART PS2 (6DR5...)
A5E03436655-02, 01/2013