Proper Mounting - Siemens SIPART PS2 6DR5 series Operating Instructions Manual

Electropneumatic positioners
Hide thumbs Also See for SIPART PS2 6DR5 series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
CAUTION
Unsuitable compressed air
Device damage. As a general rule, the positioner must only be operated with dry and clean compressed air.
● Use the customary water separators and filters. An additional dryer is required in extreme cases.
● Use dryers, especially if you operate the positioner at low ambient temperatures.
CAUTION
Prior to working on the control valve
Danger of injury.
● Before starting work on the control valve, move it into the safety position.
● Make sure that the control valve has reached the safety position.
● If you only interrupt the pneumatic auxiliary power to the positioner, it may be the case that the safety position is only
reached following a certain delay.
WARNING
Mechanical impact energy
Protect the 6DR5...0-.G...-.... version of the positioner from mechanical impact energy greater than 1 joule; this ensures
that the IP66 degree of protection is guaranteed.
When mounting, observe the following sequence imperatively to avoid injuries or mechanical damage to the
positioner/mounting kit:
1. Mount the positioner mechanically.
2. Connect the electrical auxiliary power supply.
3. Connect the pneumatic auxiliary power supply.
4. Commission the positioner.
NOTICE
Impact energy and torque
For versions 6DR5a.b-.Gc..-...., where a = 0, 2, 5, 6; b = 0, 1; c = G, N, M, P, Q, the following is applicable:
The device must be protected against power surges of over one joule.
For versions 6DR5a.b-.Gc..-...., where a = 0, 2, 5, 6; b = 0; c = G, N, M, P, Q, the following is applicable:
The maximum torque on the thread of the cable gland should not exceed 67 Nm.
3.1.1

Proper mounting

NOTICE
Incorrect mounting
The device can be damaged, destroyed, or its functionality impaired through improper mounting.
● Before installing ensure there is no visible damage to the device.
● Make sure that process connectors are clean, and suitable gaskets and glands are used.
● Mount the device using suitable tools. Refer to the information in Chapter "Constructional design (Page 36)", for
example installation torques requirements.
SIPART PS2 (6DR5...)