Connecting up

5.3 Power supply

5.3
Power supply
Notes on the power supply
Incorrect power supply
When the device is connected to a redundant power supply (two separate power supplies),
both must meet these requirements.
Never operate the device with AC voltage or DC voltage higher than 32 V DC.
Damage to the device due to overvoltage
The connector of the external power supply is not protected against strong electromagnetic
pulses that can, for example, result from lightning strikes or switching large loads.
One of the tests used to attest the immunity of devices of the IE switches SCALANCE XC-
200 to electromagnetic interference was the "surge immunity test" according to EN61000-4-
5. This test requires overvoltage protection for the power supply lines. A suitable device is,
for example, the Dehn Blitzductor BVT AVD 24, article number 918 422 or a comparable
protective element.
Manufacturer: DEHN+SOEHNE GmbH+Co. KG, Hans-Dehn-Str.1, Postfach 1640, D92306
Neumarkt, Germany
Operate the SCALANCE XC-200 with suitable overvoltage protection.
Note
The device can be disconnected from the power supply by pulling off the terminal block.
Information on the power supply
● The "L1" and "L2" LEDs indicate the current range of the power supply, see the section
"LEDs "L1" and "L2" (Page 31)".
● The power supply is connected using a 4-pin plug-in terminal block (spring-loaded
terminal). The terminal block ships with the device and can also be ordered as a spare
part.
● The power supply can be connected redundantly. Both inputs are isolated. There is no
distribution of load. When a redundant power supply is used, the power supply unit with
the higher output voltage supplies the device alone.
● The power supply is connected over a high resistance with the enclosure to allow an
ungrounded set up. The two power inputs are non-floating.
● Note the wiring rules.
50
WARNING
CAUTION
Operating Instructions, 07/2016, C79000-G8976-C442-01
SCALANCE XC-200