Signal Transmission Error (Between Indoor Unit And Outdoor Unit) - Daikin K-Series Service Manual

Floor standing
Table of Contents

Advertisement

SiBE061121.book Page 85 Monday, April 25, 2011 3:21 PM
SiBE061121
4.7
Signal Transmission Error (between Indoor Unit and
Outdoor Unit)
U4
Remote
Controller
Display
Method of
The data received from the outdoor unit in indoor unit-outdoor unit signal transmission is
checked whether it is normal.
Malfunction
Detection
Malfunction
The data sent from the outdoor unit cannot be received normally, or the content of the data is
abnormal.
Decision
Conditions
Supposed
Causes
Troubleshooting
Check No.11
Refer to P.120
Service Diagnosis
Wiring error
Breaking of the connection wires between the indoor and outdoor units (wire No. 3)
Defective outdoor unit PCB
Defective indoor unit PCB
Disturbed power supply waveform
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the indoor unit-outdoor unit
connection wires.
YES
Is there any wiring error?
NO
Check the voltage of the
connection wires on the indoor
terminal board between No. 1
and No. 3, and between No. 2
and No. 3.
YES
Properly insulated?
NO
Check the LED A on the outdoor
unit PCB.
NO
Is LED A blinking?
YES
Check No.11
Check the power supply
waveform.
NO
Is there any disturbance?
YES
Correct the indoor unit-outdoor
unit connection wires.
Replace the connection wires
between the indoor and
∗ Before you check the LED A,
outdoor units.
cancel the standby electricity
saving function by operating
fan operation with the remote
controller.
∗ Wait at least for 7 sec. after
turning on the power.
Diagnose the outdoor unit
PCB.
Replace the indoor unit PCB.
Locate the cause of the
disturbance of the power supply
waveform, and correct it.
Troubleshooting
(R14622)
85