Viessmann Vitocrossal 300 CA3 2.5 Installation And Service Instructions Manual page 167

Ca3 series gas condensing boiler with cylinder burners
Table of Contents

Advertisement

Vitocrossal 300 CA3 Series 2.5 to 6.0 Installation/Service
"Heating Circuit ..." Group
Coding in the factory set condition
"Extended economy mode"
a6:36
Extended economy mode disabled.
"Mixing valve economy function"
a7:0
Only for heating circuits with mixing
valve:
Without mixing valve economy function.
"Pump idle time"
a9:0
Without pump idle time.
"Output reduction"
aa:2
With output reduction through
temperature sensor aJA.
"Room temperature hook-up"
b0:0
With remote control:*1
Heating mode/reduced mode:
Weather-compensated.
"Room influence factor"
b2:8
With remote control and for the heating
circuit, operation with room temperature
hook-up must be programmed:
Room influence factor 8.
"Room temperature-dependent heating circuit pump logic function"
b5:0
With remote control:
No room temperature-dependent
heating circuit pump logic function.
*1 Only change the coding for the heating circuit without mixing valve A1 for boilers without lower temperature
limit or for heating circuits with mixing valve if a remote control is connected to them.
(continued)
Possible change
a6:5
to
a6:35
a7:1
a9:1
to
a9:15
aa:0
aa:1
b0:1
b0:2
b0:3
b2:0
b2:1
to
b2:31
b5:1
to
b5:8
Coding Level 2
Extended economy mode enabled,
i.e. the burner and heating circuit pump
will stop and the mixing valve will be
closed at a variable value, adjustable
between 41°F to 95°F (5°C and 35°C)
plus 2°F (1°C). The base value is
the adjusted outdoor temperature. This
value is based on the actual outdoor
temperature and a time constant, which
takes the cooling down of an average
building into consideration.
With mixing valve economy function:
Heating circuit pump also OFF:
H Mixing valve switched on to heating
circuit pump longer than 20 min:
H Mixing valve in control mode
H If there is a risk of frost
Pump idle time adjustable from 1 to 15.
1: Short idle time
15: Long idle time
Without output reduction.
No function.
Heating mode: Weather-compensated
Reduced mode:
with room temperature hook-up
Heating mode: with room temperature
hook-up
Reduced mode: Weather-compensated
Heating mode/reduced mode:
with room temperature hook-up.
Without room influence.
Adjustable from 1 to 31.
For heating circuit pump logic function,
see the following table on page 168.
167