Viessmann Vitocrossal 300 CA3 2.5 Installation And Service Instructions Manual page 157

Ca3 series gas condensing boiler with cylinder burners
Table of Contents

Advertisement

Vitocrossal 300 CA3 Series 2.5 to 6.0 Installation/Service
"Cascade" Group
Coding in the factory set condition
"Minimum system supply temperature limit"
36:0
Set to 32°F (0°C).
"Maximum system supply temperature limit"
37:80
Set to 176°F (80°C).
"Boiler section 1 or boiler sequence changeover"
38:0
No boiler section boiler sequence
changeover
Do not adjust!
"Permanent boiler section 1"
39:0
No permanent lead boiler section.
Do not adjust!
"Permanent last boiler"
3a:0
No permanent last boiler section.
Do not adjust!
"Type of control"
3b:1
Standalone parallel boiler circuit:
With supply temperature sensor
(see page 124).
"Control strategy"
3c:0
Condensing strategy (see page 125).
"Output statement"
3d:1
Output statement for condensing
strategy and conventional boiler strategy 1.
(continued)
Possible change
36:1
Adjustable from 32°F to 261°F
to
(0 to 127°C) (only when operating with
36:127
standard room temperature).
37:20
Adjustable from 68°F to 261°F
to
(20 to 127°C).
37:127
Note: Value must be lower than the
lowest value of coding "06" in the
"Combustion controller" group of every
control unit.
38:1
Boiler section 1 changeover:
Every first day of the month, the boiler
with the shortest number of hours run
by its burner becomes the boiler section 1.
38:2
Boiler section 1 changeover after 200 to
to
20,000 hours run
38:200
1 step
39:1
Permanent lead boiler section is 1, 2, 3,
to
4, 5, 6, 7 or 8.
39:8
3a:1
Permanent last boiler section is 1, 2, 3,
to
4, 5, 6, 7 or 8.
3a:8
3b:0
Standalone parallel boiler circuit:
Without supply temperature sensor
(see page 124).
3b:2
Standalone serial boiler circuit:
Without supply temperature sensor
(see page 124).
3b:3
Standalone serial boiler circuit:
With supply temperature sensor
(see page 124).
3b:4
Sequential control method with
supply temperature sensor
(see page 124).
3c:1
Conventional boiler strategy 1
(see page 126).
3c:2
Conventional boiler strategy 2
(see page 127).
3d:0
No output statement
Control only in accordance with
conventional boiler strategy 2.
Coding Level 2
100 hours run.
157