Viessmann Vitocrossal 300 CA3 2.5 Installation And Service Instructions Manual page 134

Ca3 series gas condensing boiler with cylinder burners
Table of Contents

Advertisement

Function Description
DHW Tank Temperature Control
134
Vitocrossal 300 CA3 Series 2.5 to 6.0 Installation/Service
(continued)
Tank temperature control with 2 tank temperature sensors
Coding "55:2" in the "DHW" group;
Tank temperature sensor 1 enables the DHW pump and
is evaluated for stop conditions during the pump delay
off time.
Tank temperature sensor 2:
Tank heating will start early if a lot of hot water is drawn
off. Tank heating will terminate early if no hot water is
drawn off.
DHW tank goes cold:
H Set value -5°F (–2.5 K), change at coding "59"
or...
H Actual DHW temperature at sensor 2 < set DHW
temperature x factor for start time (adjustment at
coding "69")
The DHW tank is hot:
H set value 5°F (2.5 K)
and...
H Actual DHW temperature at sensor 2 > set DHW
temperature x factor for stop time (adjustment at
coding "68")
Coding "55:3" in the "DHW" group;
tank temperature control tank loading system
The DHW tank goes cold [set value -5°F (–2.5 K); change
at coding "59"]:
H The set boiler water temperature is set 36°F (20 K)
higher than the set DHW temperature (adjustable via
coding "60").
H The primary pump in the tank loading system starts.
H The 3-way mixing valve opens and then regulates to
the specified set value.
H The DHW pump cycles (briefly switches on and off)
until the set supply temperature has been reached [set
DHW temperature +10°F (+5 K)].
Then it runs constantly. If, during heating, the actual
value falls below the required set temperature, the DHW
pump will temporarily cycle again.
The DHW tank is hot:
H Tank temperature sensor 1:
Actual value ≥ set value
and...
Tank temperature sensor 2:
Actual value > set value -3°F (–1.5 K):
H The set boiler water temperature is reset to the
weather-compensated set value.
H The DHW pump stops immediately when the 3-way
mixing valve is fully opened.
or...
H The DHW pump stops after expiry of the delay off time
that is selected at coding "62".