Viessmann Vitocrossal 300 CA3 2.5 Installation And Service Instructions Manual page 149

Ca3 series gas condensing boiler with cylinder burners
Table of Contents

Advertisement

Vitocrossal 300 CA3 Series 2.5 to 6.0 Installation/Service
"General" Group
Coding in the factory set condition
"Function output 157 at EA1 extension"
5c:0
Function output aBJ at EA1 extension:
Central fault message
"Function input DE1 at EA1 extension"
5d:0
No function
"Function input DE2 at EA1 extension"
5e:0
No function
(continued)
Possible change
5c:1
Feed pump
5c:2
No function
5c:3
Heating circuit pump, heating circuit without
mixing valve A1 (heating circuit 1), switched
to low speed (reduced mode).
5c:4
Heating circuit pump, heating circuit with
mixing valve M2 (heating circuit 2), switched
to low speed (reduced mode).
5c:5
Heating circuit pump, heating circuit with
mixing valve M3 (heating circuit 3), switched
to low speed (reduced mode).
5d:1
Operating program changeover
5d:2
External demand with minimum set supply
temperature. Set value adjustment at coding
"9b" in the "General" group.
5d:3
External blocking
5d:4
External blocking with fault message.
5d:5
Fault message input.
5d:6
Brief operation, DHW recirculation pump (push
button function) Set DHW recirculation pump
runtime at coding "12" in the "General" group.
5e:1
Operating program changeover
5e:2
External demand with minimum set supply
temperature Set value adjustment at coding
"9b" in the "General" group.
5e:3
External blocking
5e:4
External blocking with fault message.
5e:5
Fault message input
5e:6
Brief operation, DHW recirculation pump (push
button function) Set DHW recirculation pump
runtime at coding "12" in the "General" group.
Coding Level 2
149