Vitodens 100-W, B1HA series & B1KA Combi Installation/Service
Installation Examples
Vitodens 100-W, B1KA 35 with...
-
low-loss header
-
one heating circuit
Legend
AV
Air vent
PRV
Pressure relief valve (boiler)
DPRV Pressure relief valve (DHW 150 psi)
WSE Water softener equipment
DHW Domestic hot water
DCW Domestic cold water
A
Vitodens 100-W gas-fired condensing boiler
B
External boiler / system controller with room
thermostat connection (field supplied)
Heating circuit
C
D
Heating circuit pump (field supplied)
E
Low-loss header (there is no LLH temperature
sensor available for the B1KA)
F
Expansion tank
G
Outdoor temperature sensor (OTS)
(continued)
Note: The use of a low-loss header is recommended if the
water flow rate is less than 1.7 GPM (400 L/h) or
more than 6.2 GPM (1400 L/h).
The low-loss header is available as accessory part.
Maximum Flow Rates
Model B1KA
Output
 t
30ºF (17ºC) rise
35ºF (19.5ºC) rise
40ºF (22ºC) rise
* Requires low loss header or closely spaced tees.
Connections
35
MBH
117
GPM (L/h)
7.8 (1772)*
GPM (L/h)
6.7 (1522)*
GPM (L/h)
5.9 (1328)
31