Single-Boiler System With Vitocrossal 300 Boiler With Several Heating Circuits And One Modulating Flow Temperature Heating Circuit; H Circuit Diagram - Viessmann Vitocrossal 300 CT3 Technical Manual

Gas-fired condensing boiler 80 to 895 kw
Table of Contents

Advertisement

3.1 Circuit diagram 2
Circuit diagram 2
Single-boiler system with Vitocrossal 300 boiler with several heating circuits and one
modulating flow temperature heating circuit
System
Single-boiler system with:
H Vitocrossal 300 (80 to 895 kW)
H Vitotronic 300 (Type GW2)
or
Vitotronic 100 (Type GC1) with Vitocon
trol control cabinet and weather-com
pensated control unit
or
Vitotronic 100 (Type GC1) and external
weather-compensated control unit.
Possible applications:
For heating circuits with different tem
peratures.
Equipment required
(Applicable to standard systems see "Vitotec 2" Manual for systems with additional system equipment)
Item
Description
1
Boiler with Vitotronic
2
Extensions for heating circuits with mixing valve in conjunction with Vitotronic 300 (Type GW2)
Extension kit for a heating circuit with mixing valve
or
Mixing valve motor for flange-mounted mixing valve and connector
and
Contact temperature sensor
or
Immersion temperature sensor (with sensor well)
(See Price List for other heating circuit controls)
3
Maximum temperature limiter for underfloor heating system
Contact temperature sensor
or
Immersion temperature sensor (with sensor well)
30
Functional description
The Vitocrossal 300 is operated with
modulating boiler water temperature by
means of the weather-compensated
boiler control unit. Two-stage or modulat
ing burners can be controlled.
The Vitocrossal 300 has two return con
nections. The heating circuits with the
higher return temperature are connected
to the "KR 2" return connection, those
with the lower temperatures to the "KR 1"
return connection.
Please note: At least 15 % of the take-off
from the rated output must be connected
to the "KR 1" return connection.
The boiler water temperature which is es
tablished in the heating mode is higher than
the maximum heating system flow tem
perature by an adjustable difference.
Advantages
Thanks to the separate return connec
tions for heating circuits with high and
low return temperatures, high efficiencies
of up to 109 % are also achieved even
when the majority of heat consumers are
operated with high temperatures.
The two heating circuits connected to the
Vitotronic 300 are controlled without the
need for major installation work.
A remote control can be connected for
each heating circuit.
Wiring diagram
For the connection of the pumps in the
underfloor heating circuit.
20
N
L1
M
H K
L
1~
sÖ Heating circuit control unit
H Primary pump of underfloor heating
circuit
K Maximum temperature limiter for un
derfloor heating circuit 3
L Secondary pump of underfloor heat
ing circuit (after system separation)
Qty
Part No.
1
See Price List
1 or 2
7450 650
1 or 2
See Price List
1 or 2
7450 642
1 or 2
7450 641
1
7415 026
1
7415 025
M
1~