Connections
Installation Examples
Vitodens 100-W, B1KA 35 with one heating circuit
Legend
AV
Air vent
PRV
Pressure relief valve (boiler)
DPRV Pressure relief valve (DHW 150 psi)
WSE Water softener equipment
DHW Domestic hot water
DCW Domestic cold water
Vitodens 100-W
A
Room thermostat
B
C
Heating circuit
D
Expansion tank
Outdoor temperature sensor (OTS)
E
30
Vitodens 100-W, B1HA series & B1KA Combi Installation/Service
(continued)
Note: The use of a low-loss header is recommended if the
water flow rate is less than 1.7 GPM (400 L/h) or
more than 6.2 GPM (1400 L/h).
The low-loss header is available as accessory part.
Built-in pump residual head for the heating system
side is 4.3 ft. of water column at the boiler
maximum flow rate of 6.2 GPM.
Maximum Flow Rates
Model B1KA
Output
 t
30ºF (17ºC) rise
35ºF (19.5ºC) rise
40ºF (22ºC) rise
* Requires low loss header or closely spaced tees.
35
MBH
117
GPM (L/h)
7.8 (1772)*
GPM (L/h)
6.7 (1522)*
GPM (L/h)
5.9 (1328)