Power Supply - Emerson CSI 6500 Quick Start Manual

Machinery health monitor a6151, dual channel low frequency shaft vibration monitor
Hide thumbs Also See for CSI 6500:
Table of Contents

Advertisement

Available languages

Available languages

Product Information / Produktinformation A6151
Shaft Vibration Monitor
Interface RS 485
d4, z4 bus interface for communication with an MMS 68xx epro Interface card and the
configuration software.

1.6.5 Power supply

The monitor system voltages, and thus the 0 V / common connections for the measurement
and monitoring inputs and outputs, are galvanically separated.
Supply voltage inputs
Voltage input UB+ / UN+
Common reference 0 V U−
Perm. voltage range
Power consumption
Monitor system voltage
The system voltages required for the internal supply are constantly monitored. If undervoltage
is detected an error message is generated.
Sensor supply
For both channels of the monitor
Separation
Sensor supply channel 1
Sensor supply channel 2
supply voltage
Residual ripple
Max. current
Max. short−circuit current
Two redundant diode decoupled inputs for nominal
+24 V with common 0 V reference
d2 / z2
b2
19 ... 31.2Vdc (IEC 654−2 class DC 4)
CSA: 24Vdc; SELV LPS
max. 6 W, at 24 V max. 250 mA
Decoupled and galvanically separated from the
supply voltage, can be operated in parallel with other
monitors, open circuit and short circuit proof, non
reactive.
Supply1(−) / Supply1(+) b6/z6
Supply2(−) / Supply2(+) b8/d6
26.75 V DC; Tolerance ±2
< 20 mVpp (at nominal current 20 mA)
35 mA
0 mA ≤ I short−circuit ≤ 5 mA;
Open circuit and short−circuit proof