5.6.2
Enclosure ambient temperature
Drive derating is required for operation in high ambient temperatures
Totally enclosing or through panel mounting the drive in either a sealed
cabinet (no airflow) or in a well ventilated cabinet makes a significant
difference on drive cooling.
The chosen method affects the ambient temperature value (T
should be used for any necessary derating to ensure sufficient cooling
for the whole of the drive.
The ambient temperature for the four different combinations is defined
below:
1. Totally enclosed with no air flow (<2 m/s) over the drive
T
= T
+ 5° C
rate
int
2. Totally enclosed with air flow (>2 m/s) over the drive
T
= T
rate
int
3. Through panel mounted with no airflow (<2 m/s) over the drive
T
= the greater of T
+5°C, or T
rate
ext
4. Through panel mounted with air flow (>2 m/s) over the drive
T
= the greater of T
or T
rate
ext
Where:
T
= Temperature outside the cabinet
ext
T
= Temperature inside the cabinet
int
T
= Temperature used to select current rating
rate
5.6.3
Altitude derating
Multiply the maximum rated output current by the derate factor (Df) in
Figure 5-31 and the ambient correction factor (Cf) in Figure 5-32.
Rated output current = Df x Cf x Oc
Figure 5-31 Altitude derate factor
1
0.95
0.9
0.85
0.8
0.75
0
500
64
Product information
configuration
rate
int
int
1000
1500
2000
2500
3000
Altitude (m)
System
Mechanical
Installation
Figure 5-32 Ambient temperature correction factor
1.035
1.03
1.025
) which
1.02
1.015
1.01
1.005
1
0.995
20
22
NOTE
The ambient temperature correction factor used is for altitude
calculation only. If the ambient is less than 40°C the drive cannot be
over rated. The maximum permissible output currents should remain
the same as those given at 40 °C.
If the drive is required to operate above 40 °C the derates at 50 °C
should be applied.
The same applies for altitude below 1000 m. There should be no
over rating at lower altitude
NOTE
For applications over 3000 m, contact the supplier of the drive.
5.6.4
Enclosure sizing
This section looks at a method for cooling a medium power density
enclosure. By running through a worked example it brings out the issues
associated with cooling the drives when they are completely mounted
inside an enclosure.
This example only considers one possible method of enclosing the
drives and tries to highlight and solve thermal issues created by hot air
recirculating inside an enclosure. Other methods of enclosure design are
also possible, such as through panel mounting, which removes many of
the issues discussed in this chapter. Refer to section 5.5.2 Through-
panel mounting on page 54.
The enclosure design example will use the following conditions:
Enclosure placed in a room with a 30°C ambient and an altitude
<1000 m
Continuous output current requirement from the system = 650 A
Parts used in system model:
1800 mm (70.87 in) x 800 mm (31.5 in) x 500 mm (19.69 in)
enclosure with input and output ventilation
2 x 10402700
2 x input line reactors (L1)
2 x output sharing chokes (L2)
Unidrive M / Unidrive HS Modular Installation Guide
Electrical
Technical data
Installation
24
26
28
30
32
°
Temperature ( C)
UL Information
34
36
38
40
Issue Number: 5