Communication Status; Operation Using Process Data - WEG SCA06 User Manual

Ethernet communication module
Hide thumbs Also See for SCA06:
Table of Contents

Advertisement

3. For the master configuration, in addition to the IP address used by the EtherNet/IP module, you must indicate
the number of instances of I/O and the amount of data exchanged with the master in each instance. For the
communication module for EtherNet/IP, the following values must be programmed:
Input instance: 100
Output instance: 150
4. The EtherNet/IP module is described as "Generic Ethernet Module" on the device list. Using these settings you
can program the network master to communicate with the equipment.
8.6.4

Communication Status

Once you install the network and program the master, you can use the LEDs and equipment parameters to identify
some states related to communication.
The LEDs "NS" and "Link" provide information about the state of the interface and communication.
The parameter P0801 indicates the status of communication between the device and the network master.
The network master must also provide information about the communication with slave.
8.6.5

Operation Using Process Data

Once the communication is established, the data mapped in the I/O area is automatically updated between master
and slave. Among the main parameters that can be used to control the device, we can mention:
Status Word
Motor Speed
Torque Current
Present Control Mode
Control Word
Speed Reference
Torque Reference
Control Mode
It is important to know these parameters to program the master as desired for the application.
EtherNet/IP
SCA06 | 30