P0810 - Ip Address Configuration; P0811 - Ip Address 1; P0812 - Ip Address 2; P0813 - Ip Address 3 - WEG SCA06 User Manual

Ethernet communication module
Hide thumbs Also See for SCA06:
Table of Contents

Advertisement

P0810 – IP ADDRESS CONFIGURATION
Range:
Properties:
Description:
It allows to choose how to set the IP address for the Ethernet modules.
Option
0 = Parameters
1 = DHCP
NOTE!
For the changes in this parameter be effective, the equipment must be powered off and on again, or
an update must be performed by P0849.
P0811 – IP ADDRESS 1
P0812 – IP ADDRESS 2
P0813 – IP ADDRESS 3
P0814 – IP ADDRESS 4
Range:
Properties:
Description:
If P0810 = 0 (parameters), these parameters allow you to program the IP address of the Ethernet module. For other
option of P0810, these parameters have no function.
Each parameter programs one octet of the IP address, where the P0811 is the most significant octet. The pro-
grammed IP address, then, has the format "P0811.P0812.P0813.P0814".
NOTE!
For the changes in this parameter be effective, the equipment must be powered off and on again, or
an update must be performed by P0849.
P0815 – SUBNET CIDR
Range:
Properties:
Description:
If P0810 = 0 (parameters), this parameters allow you to program the sub-net mask for the Ethernet module. The
subnet mask can usually be programmed using a notation with 4 octets separated by dots, or CIDR notation, in
which the value is the number of bits with value "1" in the subnet mask. For other option of P0810, this parameter
has no function.
0 = Parameters
1 = DHCP
RW, ETH
Table 5.4: P0810 options
The settings for IP address, sub-net mask and gateway shall be done by means of
parameters P0811 to P0819.
Enables DHCP function. A DHCP server should set the IP address, sub-net mask and
gateway through network.
0 ... 255
RW, ETH
1 ... 31
RW, ETH
Description
Default: 192.168.0.10
Parameterization
Default: 1
Default: 24
SCA06 | 17