Level transmitters with hart and modbus

Advertisement

Quick Links

Quick Start Guide
00825-0500-4530, Rev AC
February 2017
Rosemount
VeriCase User Guide
Rosemount 3308 and 5300 Series Level Transmitters
®
®
with HART
and Modbus

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 3308 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Rosemount 3308 Series

  • Page 1 Quick Start Guide 00825-0500-4530, Rev AC February 2017 ™ Rosemount VeriCase User Guide Rosemount 3308 and 5300 Series Level Transmitters ® ® with HART and Modbus...
  • Page 2: Table Of Contents

    D. Temperature display Contents Rosemount VeriCase overview ....2 Performing a verification on a Rosemount 3308 transmitter ......6 Check Rosemount VeriCase and verification sheet 3 Generating a report .
  • Page 3: Check Rosemount Vericase And Verification Sheet

    Power-up the Rosemount VeriCase The Rosemount VeriCase can be powered by either a 110V/220V power supply or a 12VDC power adapter supplied with the Rosemount VeriCase. In order to power-up the Rosemount VeriCase and connect to a transmitter head, follow the steps below;...
  • Page 4: Performing A Verification On A Rosemount 5300

    Performing a verification on a Rosemount 5300 transmitter Before you start Open Rosemount Radar Master and record the serial number and firmware  revision of the device to be tested in the verification data tab of the workbook. This information can be found in the device properties window in the 'device' menu in Rosemount Radar Master.
  • Page 5 Verification test 1. Set the Cable Switch to position 1. Wait for the values to stabilize before taking a reading from the Device Display window in Rosemount Radar Master. 2. Record the distance value, internal temperature of transmitter and Rosemount VeriCase temperature.
  • Page 6: Performing A Verification On A Rosemount 3308

    Select Receive. When the values have finished loading select File and Save Memory. Note When reading a measurement value remember that the repeatability of a Rosemount 3308 is ± 2mm (0,08-in.) 2. In the Setup window under the Setup menu, configure the following...
  • Page 7 Rosemount VeriCase temperature. 3. Repeat the procedure in for all six cable lengths in the Rosemount VeriCase. 4. Once the verification is complete, restore the original configuration by uploading the memory map to the transmitter. Select File from the top menu and Open Memory Map.
  • Page 8: Generating A Report

    February 2017 Quick Start Guide 5. After the configuration has been restored, disconnect communication to the transmitter. Generating a report Once testing is complete, a report can be generated from the Excel workbook. It is possible to generate a verification report and/or a Q4 certificate by selecting the corresponding generate report buttons located at the bottom of the verification data tab and the Q4 data tab respectively.
  • Page 9: Appendix

    Q: How do I know if a device has passed the test? A: Refer to the Rosemount 5300 PDS for accuracy specifications. A device has passed if the final result is inside the combined accuracy for the Rosemount 5300 and the Rosemount VeriCase as shown in the Excel workbook.
  • Page 10 The Emerson logo is a trademark and service mark of Emerson Electric Co. Middle East and Africa Regional Office Rosemount and Rosemount logotype are trademarks of Emerson. Emerson Automation Solutions HART is a registered trademark of the FieldComm Group. Emerson FZE P.O. Box 17033 Modbus is a registered trademark of Gould Inc.