7.TROUBLE SHOOTING:
2. When the unit has the following trouble and the compressor stops running, press the sleep button on
the remote controller for 4 times in ten seconds and the 7-segment tube of the display board will show the
error code as the following, if two malfunction happened at the same time, it need press the sleep button for
4 times again, the LED will show the other error code.
Refer to the remote controller which the sleep key can set into 4 different combination ways (Hisense's
new design remote controller), when using to check the error codes only takes effect for pressing the sleep
key 10 times in ten seconds instead of 4 times.
NOTE: If the troubleshooting inquiry display by 7-segment tube, then the error code will be displayed,
otherwise only the LED of the display board can show.
Power
Timer
Error
code
1
2
1
x
o
33
o
x
34
o
x
38
o
39
o
x
41
42
o
o
Remark:★Light
Running
Sleep
3
4
Content
The failure for
x
x
temperature sensor of
outdoor coil
The failure for
x
temperature sensor of
indoor room
The failure for
x
temperature sensor of
indoor coil temperature
Indoor EEPROM failure
Indoor fan motor run
abnormally
The failure for Indoor
x
grounding protective
x
Overcooling protection
o
x
Flash
OFF
The root cause is may be one of the
Remark
following
a.
The outdoor temperature sensor loose;
b.
The outdoor temperature sensor is
Heat pump
failure;
c.
The indoor control board is failure
a.
The indoor room temperature sensor
loose;
b.
The indoor room temperature sensor is
failure;
c.
The indoor control board is failure.
a.
The indoor coil temperature sensor
loose;
b.
The indoor coil temperature sensor is
failure;
c.
The indoor control board is failure.
a.
The EEPROM chip loose;
b.
The indoor control board is failure
a.
There are something block the indoor fan
motor;
7k,9k,12k,
b. The fan motor cord connect loose;
18K
c. The fan motor is failure;
d. The indoor control board is failure
The indoor control board is failure
a.
It is normally for protection, When the
indoor pipe temperature below
T<-1℃(-7℃).Outdoor fan motor and
compressor will stop running. When the
Indoor pipe temperature is higher than
7k,9k=-1℃
-1(-7℃),the unit will restart normally
12k=-7℃
b.
The indoor coil temperature sensor is
loose;
c.
The indoor coil temperature sensor is
failure;
d.
The indoor control board is failure.