1MRS752278
3.4.5.
3.4.5.1.
COM600 series, Version 5.0
IEC 60870-5-103 Master (OPC) User's Manual
Name
Value or Value range/
Default
Time Synchroniza-
0...65535
tion Interval
Default: 15
Control Authoriza-
tion
Station/Remote
Default: None
Switch OPC Path
OPC Alarm and
Event
Device Connection
Default: Device Connec-
status Class
tion Status
Data objects for status information
General information about data objects for status information
There are seven different data objects providing status information:
•
3.4.5.2, Single point status (SPS)
•
3.4.5.3, Double point status (DPS)
•
3.4.5.4, Integer status (INS)
•
3.4.5.5, Enumerated Status (ENS)
•
3.4.5.6, Protection activation information (ACT)
•
3.4.5.7, Directional protection activation information (ACD)
•
3.4.5.8, Device name plate (DPL)
•
3.4.5.9, Logical node name plate (LPL)
The parameters are stored in Object Properties of SAB600, see the tables for each data
object type. The actual configuration using SAB600 is performed as described in
3.4.1, General information about configuring objects.
Description
Time synchronization interval in seconds
OPC path of the station remote switch position is
used with this device. The format is Node#ProgID
For OPC Server#Channel Name\IED Name\Logical
Device Name\Logical Node Name\Data Object
Name e.g.
GW#ABB.IEC103_OPC_DA_Server.Instance[1]#Chan-
nel1\IED1\LD1\GGIO1\loc
Device connection status class definition used with
current device.
25