1MRS752278
3.3.2.
3.3.3.
3.3.4.
3.3.5.
COM600 series, Version 5.0
IEC 60870-5-103 Master (OPC) User's Manual
Adding Gateway object
To start building the object tree, add a Gateway object in the Communication structure
by selecting the project name, right-click it and select New > Communication > Gate-
way.
Adding IEC103 OPC Server object
After the Gateway object has successfully been added, you can continue building the
object tree by adding an IEC103 OPC Server object.
To add an IEC103 OPC Server object:
1. Select the Gateway object in the communication structure and right-click it.
2. Add an IEC103 OPC Server object.
By using the SCL Import function, it is possible to import an entire server's or individual
device's configurations without having to insert them manually. To open the SCL Import
function, right-click the desired object, and select SCL Import.
For more information about the SCL Import function, see COM600 User's Manual.
Connectivity Packages for certain protection and control devices can also support other
ways to build this structure, depending on the configuration of an individual device, for
example device-related object types and wizards. Typically, Connectivity Packages
include SCL description files which must be installed. For further information on these
Connectivity Packages, see the Connectivity Package of a certain device in the product
documentation.
Adding IEC103 Channel objects
To add an IEC103 Channel object:
1. Select an IEC103 OPC Server object and right-click it.
2. Add an IEC103 Channel object.
3. Rename the new object. The names of the IEC103 Channels have to be unique.
Adding IEC103 Device objects
To add an IEC103 Device object:
1. Select an IEC103 Channel object and right-click it.
2. Add an IEC103 Device object.
3. Rename the new object. The names of the IEC103 Devices within an IEC103 OPC
Server have to be unique.
19