Fujitsu ASU18RMLQ Service Instruction page 52

Split type room air conditioner
Hide thumbs Also See for ASU18RMLQ:
Table of Contents

Advertisement

Trouble shooting 19
OUTDOOR UNIT Error Method:
Heat Sink Temperature
Thermistor Error
Detective Actuators:
Outdoor Unit Main PCB Circuit
Heat Sink Temperature Thermistor
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 2 :
Thermistor Characteristics (Approx. value)
Temperature
Resistance Value (k )
Temperature
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
1 2
1 2
CN25
CN26
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When Heat Sink Temperature Thermistor open or short-circuit is
detected at power ON or while running the compressor.
32°F
41°F
50°F
59°F
(0°C)
(5°C)
(10°C)
(15°C)
16.1
12.4
9.73
140°F
158°F
176°F
194°F
(60°C)
(70°C)
(80°C)
(90°C)
1.25
0.89
0.65
1 2
1 2
1 2
CN23
CN22
CN21
02-26
68°F
86°F
104°F
(20°C)
(30°C)
(40°C)
7.67
6.10
3.95
2.62
212°F
230°F
248°F
(100°C)
(110°C)
(120°C)
0.48
0.36
0.27
0.21
122°F
(50°C)
1.79

Advertisement

Table of Contents
loading

Table of Contents