Fujitsu ASU18RMLQ Service Instruction page 43

Split type room air conditioner
Hide thumbs Also See for ASU18RMLQ:
Table of Contents

Advertisement

Trouble shooting 10
INDOOR UNIT Error Method:
Indoor Fan Motor abnormal
Detective Actuators:
Indoor Unit Control PCB (AS,AR),
Main PCB, Power PCB (AU) Circuit.
Indoor Fan Motor
Forecast of Cause:
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Control PCB (AS,AR),
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Check Point 3 : Replace Control PCB
If Check Point 1,2 do not improve the symptom, change Control PCB (AS,AR),
Main PCB ,Power PCB (AU)
Indicate or Display:
Refer to error code table.
Detective details:
When the condition that actual frequency of Indoor Fan is below 1/3
of target frequency is continued more than 56 seconds.
Or the condition of fan speed is 0rpm is continued more than 56 seconds.
02-17
Main PCB ,Power PCB (AU)