Trouble shooting 4
INDOOR UNIT Error Method:
INDOOR UNIT
Indoor Heat Exchanger Temperature
Thermistor Error
Detective Actuators:
Indoor Unit Control PCB (AS, AR) ,
Main PCB (AU) or Room Temperature
Thermistor
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Control PCB (AS,AR),MainPCB (AU) failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 2 :
Thermistor Characteristics (Approx. value)
Temperature
Resistance Value (k )
Temperature
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
GRAY
1
GRAY
2
BLACK
1
BLACK
2
If the voltage does not appear, replace Controller PCB(AS, AR), Main PCB(AU).
Indicate or Display:
Refer to error code table.
Detective details:
When Heat Exchanger Temperature Thermistor open or short-circuit is
detected at power ON.
32°F
41°F
50°F
59°F
(0°C)
(5°C)
(10°C)
(15°C)
176
134
103
104°F
113°F
122°F
(40°C)
(45°C)
(50°C)
25.6
20.8
17.1
THERMISTOR
(PIPE TEMP.)
THERMISTOR
(ROOM TEMP.)
02-11
68°F
77°F
86°F
(20°C)
(25°C)
(30°C)
80.3
62.9
49.7
39.6
95°F
(35°C)
31.7