Fujitsu ASU18RMLQ Service Instruction page 45

Split type room air conditioner
Hide thumbs Also See for ASU18RMLQ:
Table of Contents

Advertisement

Trouble shooting 12
OUTDOOR UNIT Error Method:
Compressor Temperature
Thermistor Error
Detective Actuators:
Outdoor Unit Main PCB Circuit
Compressor Temperature Thermistor
Forecast of Cause :
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 2 :
Thermistor Characteristics (Rough value)
Temperature
Resistance Value (k )
Temperature
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
1 2
1 2
CN25
CN26
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When Compressor Temperature Thermistor open or short-circuit is
detected at power ON or while running the compressor.
32°F
41°F
50°F
59°F
(0°C)
(5°C)
(10°C)
(15°C)
176
135
105
81.8
158°F
176°F
194°F
212°F
(70°C)
(80°C)
(90°C)
(100°C)
8.78
6.31
4.61
3.43
1 2
1 2
1 2
CN23
CN22
CN21
02-19
68°F
86°F
104°F
122°F
(20°C)
(30°C)
(40°C)
(50°C)
64.5
41.1
26.9
18.1
248°F
284°F
320°F
356°F
(120°C)
(140°C)
(160°C)
(180°C)
1.98
1.21
0.77
0.51
140°F
(60°C)
12.5

Advertisement

Table of Contents
loading

Table of Contents