Trouble shooting 3
INDOOR UNIT Error Method:
INDOOR UNIT
Room Temperature Thermistor Error
Detective Actuators:
Indoor Unit Control PCB(AS, AR) ,
Main PCB(AU) or Room Temperature
Thermistor
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Control PCB (AS,AR),MainPCB (AU) failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
Resistance Value (k )
Temperature
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 :
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
GRAY
1
GRAY
2
BLACK
1
BLACK
2
If the voltage does not appear, replace Controller PCB(AS, AR), Main PCB(AU).
Indicate or Display:
Refer to error code table.
Detective details:
When Room Temperature Thermistor open or short-circuit is
detected at power ON.
32°F
41°F
50°F
59°F
(0°C)
(5°C)
(10°C)
(15°C)
33.6
25.9
20.2
104°F
113°F
122°F
(40°C)
(45°C)
(50°C)
5.30
4.35
3.59
THERMISTOR
(PIPE TEMP.)
THERMISTOR
(ROOM TEMP.)
02-10
68°F
77°F
86°F
(20°C)
(25°C)
(30°C)
15.8
12.5
10.0
8.04
95°F
(35°C)
6.51

Advertisement

Table of Contents
loading

Table of Contents