Combustion air intake and exhaust pipes
10
Combustion air intake and exhaust pipes
Both pipes must be installed falling away from the heater. If this is not
possible, make a ø 4 mm condensation drain hole at the lowest point.
Fig. 18: Prevent condensation forming
The pipes must not face in the direction of travel.
Fig. 19: Pipe ends not facing in direction of travel
The pipes must be arranged in such a way that it cannot become clogged
with dirt.
60
Fig. 20: Prevent pipes becoming clogged with dirt
ATTENTION:
Risk of fire if the exhaust pipe ends other than shown in Fig. 21!
Length of combustion air intake and exhaust pipe in total:
with silencer:
max. 2.0 m
without silencer:
max. 5.0 m
NOTE:
Exhaust pipes longer than 2 m must be insulated (to prevent dropping below
dew point)
Inside diameter of pipes:
Combustion air line:
22 mm
Exhaust pipe (metal):
22 mm
Smallest bending radius: 50 mm
Total bends:
combustion air line: max. 270°
Exhaust pipe:
max. 270°
Air Top 2000 STC