Section 10
Testing functionality by secondary injection
10.12.1.2
10.13
100
Completing the test
Continue to test another function or end the test by changing the TESTMODE setting
to Off. Restore connections and settings to their original values, if they were changed
for testing purposes.
Exit test mode
The following procedure is used to return to normal operation.
1.
Navigate to the test mode folder.
2.
Change the On setting to Off. Press the 'E' key and the left arrow key.
3.
Answer YES, press the 'E' key and exit the menus.
1MRK 504 160-UEN -
Transformer protection RET650 2.1 IEC
Commissioning manual