How To Undo Forcing Changes And Return The Ied To Normal Operation; Undo Forcing By Using Testmode Component; Undo Forcing By Using Lhmi; Undo Forcing By Using Pcm600 - ABB RET650 2.1 IEC Commissioning Manual

Transformer protection
Table of Contents

Advertisement

Section 9
Testing IED operation
9.8.4
9.8.4.1
9.8.4.2
9.8.4.3
64
IEC15000032 V1 EN
Regardless if the forcing changes are commited or canceled, the
forcing is still active.
To force more signals, click the button Start editing signal value for forcing again.
How to undo forcing changes and return the IED to normal
operation
Regardless of which input/output signals have been forced, all forced signals will
return to their normal states immediately when the IED is taken out of test mode.
When the forcing is removed by exiting from IED test mode, both
input and output signals may change values. This means that logic
input signals may activate functions in the IED and that output relays
may change state, which can be potentially dangerous.

Undo forcing by using TESTMODE component

If the IED test mode was entered through the test mode function block:
1.
Deactivate the control input on that block.
This immediately undoes all forcing, regardless of how it was accomplished and
disabled all the way to force signals.

Undo forcing by using LHMI

If the IED test mode was enabled to using the LHMI:
1.
Set IEDTestMode to Off in the LHMI menu.
2.
Exit from the menu and click Yes in the Save dialogue box.
This immediately undoes all forcing, regardless of how it was accomplished and
disabled.

Undo forcing by using PCM600

1MRK 504 160-UEN -
Transformer protection RET650 2.1 IEC
Commissioning manual