Troubleshooting for Non Inverter Cooling Only
8-3. Troubleshooting for Non Inverter Cooling Only
8-3-1. Items to be checked first
1) The input voltage should be rating voltage ±10% range.
The airconditioner may not operate properly if the voltage is out of this range.
2) Is the link cable linking the indoor unit and the outdoor unit linked properly?
The indoor unit and the outdoor unit shall be linked by 3 cables.
Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables.
Otherwise the airconditioner may not operate properly.
3) When a problem occurs due to the contents illustrated in the table below it is a symptom not related to the
malfunction of the airconditioner.
NO
Operation of air conditioner
1
The OPERATION indication LED blinks when a
power plug of the indoor unit is plugged in for the first time.
2
In a COOL operation mode, the compressor does not
operate at a room temperature higher than the setting
temperature that the INDOOR FAN should operate.
3
Fan speed setting is not allowed in AUTO or DRY mode.
4
Compressor stops operation intermittently in DRY mode.
5
The compressor stops intermittently in a COOL mode or DRY
mode, and fan speed of the indoor unit decreases.
4)
Indoor unit observes operation condition of the air conditioner, and displays self diagnosis details on the display panel.
Description
Indoor unit room temperature sensor error(open or short)
Indoor unit heat exchanger temperature sensor error(open or short)
Indoor fan motor malfunction
EEPROM error
Option error(option wasn't set up or option data error)
(12K)
(12K)
Explanation
It indicates power is on. The LED stops blinking if the operation
ON/OFF button on the remote control unit is pushed.
In happens after a delay of 3 minutes when the compressor is
reoperated. The same phenomenon occurs when a power is on.
As a phenomenon that the compressor is reoperated after a delay
of 3 minutes, the indoor fan is adjusted automatically with reference
to a temperature of the air blew
The speed of the indoor fan is set to LL in DRY mode.
Fan speed is selected automatically in AUTO mode.
Compressor operation is controlled automatically in DRY mode
depending on the room temperature and humidity.
The compressor stops intermittently or the fan speed of the indoor
unit decreases to prevent inside/outside air frozen depending on
the inside/outside air temperature.
LAMP of Display Monitor
TURBO
OPERATION
: Lamp off
1
8
TROUBLESHOOTING
TIMER
SAVING
: Lamp flickering
SAMSUNG | 85