6
FEATURES & OPERATION
Details for Operation Property
6-2-6. Indoor fan control in the Heating Mode
Indoor fan is controlled depending on the temperature of indoor heat exchanger in the heating mode.
INDOOR FAN CONTROL
When compressor begins operating
The temperature of indoor heat exchanger
When compressor stops operating
The temperature of indoor heat exchanger
after 10 minutes when compressor stops operating
Setting speed
48 | SAMSUNG
below 28°C
28°C ~ below 34°C
34°C ~ below 40°C
above 40°C
above 20°C
below 20°C
When compressor is on
40°C
34°C
28°C
20°C
L Speed
LL Speed
OFF
OFF
Compressor
(Cont.)
When compressor is off
UL
ON
OFF
Indoor fan speed
off
LL speed
L speed
setting speed
Indoor fan speed
UL speed
off
off