WJ200 series Inverter parameter setting for solar water pump inverter
After giving power to inverter, It show 0000 value of d001 parameter (output motor Hz)
Make b049 = 01 for making inverter in Variable torque mode (Specially pump application)
Check A017 = 02 For enabling MPPT algorithm, 00 means stop, 01 means for
terminal enabling
Note : Make B037 = 00
First to set motor data inside of inverter like KW, Hz, RPM, Current, Votlage
A003 = Hz of motor
H003 = KW of motor
H004 = Pole of motor which come from RPM of motor.
A002 = 01 Terminal Run command
F002 = 100 Sec , Acceleration Time
F003 = 1 Sec , Deceleration time
A020 = Put Total Vmp of connect PV cells,
C001 = 56, Terminal 1 as Forward Run command
C006 = 18, Terminal 6 as Reset inverter
P101 = 3 min,
Auto restart delay time after inverter get any alarm, Change as per requirements
P102 = 3000, Water level sensitivity,
For 1-PHASE (2-WIRE) PUMPS MAKE :
1- P129 = 00
2- A082 = MAX
For 60Hz Pump Make :
1- A017 = 00
2- P117 = 6000
3- A061 = 60
4- A003 = 60
5- A017 = 02